• How to Cancel LL and L Alarms

1) Press [UP] or [DOWN] buttons until the indicator comes 

to the lower limit (digital indicator shows “----”), and 

press [SET].  

  LL indicator must be set before L as the L setpoint can-

not go below the LL setpoint.

 

LL (or L, H, HH, 1, 2) ALARM ON TIME DELAY

1) Hold down [M] for 3 seconds* and push [M] to choose 

[LL].

2) Press [UP] and [DOWN] buttons at once.  Current setting 

value in seconds is shown at the right end of the digital 

indicator, with ‘d.’ at the left end.

  Factory default setting is “0”.
3) Press [UP] or [DOWN] buttons until the meter shows the 

desired value, and press [SET]. (The range between 0 to 

15 sec. can be set.)

  (Same procedure for L, H, HH, 1, 2 setpoints)

 

MOVING AVERAGE SAMPLE NUMBER

1) Hold down [M] for 3 seconds* and push [M] to choose [P].
2) Press [UP] and [DOWN] buttons at once.  Current setting 

value is shown at the right end of the digital indicator, 

with ‘A.’ at the left end.

  Factory default setting is “4”.
3) Press [UP] or [DOWN] buttons until the indicator shows 

the desired value (1, 2, 4, 8 or 16), and press [SET].

 

LED BRIGHTNESS ADJUSTMENT

1) Hold down [M] for 3 seconds* and push [M] to choose [P].
2) Press [UP] and [DOWN] buttons at once for two times.  

Current setting value is shown on the digital indicator, 

with ‘c.’ at the left end.  Factory default setting is ‘7,’ the 

brightest.

3) Press [UP] or [DOWN] buttons until the indicator shows 

the desired setting (1 through 7), and press [SET].

 

RESET TO FACTORY SETTING

1) Hold down [M] for 3 seconds* and press [M] to choose [P].
2) Press [UP] and [DOWN] buttons at once for three times.
  ‘RSET’ starts blinking on the digital indicator.
3) Press [SET] and [DOWN] buttons at once.

*  The [M] button remain activated for 1 minute after it has 

been used to choose a indicator LED (programming mode).  
During this period, pressing the [M] button briefly is enough 
to choose another indicator.  After 1 minute, it turns to deac-
tivated state.

CALIBRATION PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the indication to a receiving instrument or in 
case of regular calibration, adjust the output as explained 
in the following.

 

HOW TO CALIBRATE THE OUTPUT INDICATION

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust bargraph and digital 

indicator to 0% following the procedure explained in “AD-

JUSTMENT PROCEDURE.”

2) SPAN:  Apply 100% input and adjust bargraph and digi-

tal indicator to 100% following the same procedure.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular checking procedure is explained below:

 

CHECKING

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the bargraph 
and digital indicator for the respective input signal remains 
within accuracy described in the data sheet.  When the bar-
graph and digital indicator are out of tolerance, recalibrate 
the unit according to the “CALIBRATION PROCEDURE” 
explained earlier.

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protectors for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for 48NDT

Page 1: ...fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures t...

Page 2: ...CLUSTERED MOUNTING Not conform to degree of protection IP65 1 0 61 5 min USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel...

Page 3: ...to the connection diagram on the side of the unit Attach the CJC sensor together with input wiring to the input terminals The CJC sensor is not interchangeable Do not remove No 2 terminal screw so th...

Page 4: ...4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 CONNECTION DIAGRAM T C comp leadwire T C comp leadwire T C comp leadwire 12 13 14 15 16 12 13 14 15 16 LLa 11 La...

Page 5: ...orange green green red red red H L 50 40 30 20 10 0 10 20 30 40 50 100 SET H S P Z L 90 80 70 60 50 40 30 20 10 0 SET ENTER Button H Setpoint Adj Alarm Function Span Adj Setting Decimal Point Position...

Page 6: ...lay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjust...

Page 7: ...inuous ON state 4 Press UP or DOWN buttons until the bargraph shows 0 and the digital indicator comes to a desired value and press SET DIGITAL INDICATOR ZERO ADJUSTMENT 1 Hold down M for 3 seconds and...

Page 8: ...1 minute after it has been used to choose a indicator LED programming mode During this period pressing the M button briefly is enough to choose another indicator After 1 minute it turns to deac tivat...

Reviews: