ADJUSTMENT PROCEDURE

L

SET

L

M

Increase / Decrease

L Setpoint

Complete

LL

SET

LL

M

Increase / Decrease

*

 LL Setpoint

Complete

H

SET

H

M

Increase / Decrease

H Setpoint

Complete

HH

SET

HH

M

Increase / Decrease

*

 HH Setpoint

Complete

LED OFF

LED OFF

LED Blinking

Mode Selector

*

1

UP / DOWN Button

LED Blinking

Mode Selector

*

1

 

ZERO ADJUSTMENT

: Apply 0% input signal before adjustment.

Z

SET

Z

M

Zero Adjustment

Complete

LED OFF

LED Blinking

Mode Selector

*

1

S

SET

S

M

Span Adjustment

Complete

 

SPAN ADJUSTMENT

: Apply 100% input signal before adjustment.

 

ALARM SETTING

: Proceed after the zero / span adjustments.

*

1. Keep pressing at least for 3 seconds to activate Mode Selector M.  Press briefly for second and more times within 1 minute after it has been activated.

*

2. HH or LL setpoints are not provided for the 48NAM-2.

Note: Each setting sequence is complete only when SET button is pressed.  Once set, parameters are not lost even after the power is removed, except 
          for the power saving mode.  The power saving mode is automatically cancelled when the power is reset.

SET

M

Indicator OFF

Complete

SET

M

Indicator ON

Complete

LED ON

LED OFF

LED Blinking

Mode Selector

*

1

 

POWER SAVING MODE

Summary of Contents for 48NAM

Page 1: ...con figurations connected devices connected wires may affect the protection level of this unit when it is integrated in a panel system The user may have to review the CE or UKCA requirements in regard...

Page 2: ...ENT IDENTIFICATION 50 40 30 20 10 0 10 20 30 40 50 m3 h 100 SET H S Z L 90 80 70 60 50 40 30 20 10 0 M Brackets Body A Scale Plate Pull up the part A when replacing the scale plate INSTALLATION PANEL...

Page 3: ...mm Slide the top and bottom parts of the bezel into the back of the front cover as shown below Bezel When multiple units are to be clustered side by side insert one bezel between two units as shown be...

Page 4: ...13 14 15 16 16 M3 SCREW TERMINALS Rounded corners for the option D 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 OPTION D BEZEL 3 1 Space required when replacing the scale plate 2 Used for the existi...

Page 5: ...HHa 7 Hc HHc HHb Ha HH OUTPUT H OUTPUT LL OUTPUT L OUTPUT ALARM OUTPUT CODE 2 2 points ALARM OUTPUT CODE 4 4 points 3 2 1 POTENTIOMETER max min 3 2 1 POTENTIOMETER max min U V La Lb Lc Hc Ha Hb H OUT...

Page 6: ...r amber Zero Adj amber L Setpoint Adj Trip Indicator green UP Button Mode Selector DOWN Button H Setpoint L Setpoint PV Indicator M 50 40 30 20 10 0 10 20 30 40 50 m3 h 100 SET L Z S 90 80 70 60 50 40...

Page 7: ...LED OFF LED Blinking Mode Selector 1 S SET S M Span Adjustment Complete SPAN ADJUSTMENT Apply 100 input signal before adjustment ALARM SETTING Proceed after the zero span adjustments 1 Keep pressing...

Page 8: ...ter it has been used to choose a indicator LED programming mode During this period pressing the M button briefly is enough to choose another indicator After 1 minute it turns to deac tivated state CAL...

Reviews: