background image

10VF2

P. 2 / 2

EM-0827

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such 
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive 
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this 
warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original 
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED 
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR 
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST-
MENT PROCEDURE” explained earlier.

EXTERNAL DIMENSIONS

  unit: mm (inch)

130 (5.12)

3 (.12)

50 (1.97)

82

 (3

.23

)

2–4.3 (.17) dia.

MTG HOLE

TERMINAL COVER

7–M3.5 SCREW

8 (.31)

91

 (3

.58

)

99

 (3

.90

 )

25 (.98)

1 2

3

5 6

7 8

Reviews: