10TS / 10TK

P. 2 / 2

EM-0812 Rev.3

CHECKING

1) Terminal wiring:  Check that all cables are correctly

connected according to the connection diagram.

2) Power input voltage:  Check voltage supplied to the rack

(model: 10BX

).  For the DC power source, be sure that

the ripple level is within 10% p-p.

3) Input:  Check that the input voltage is within 0 – 100% of

full-scale.
If the thermocouple or its extention wires are broken, the
output goes over 100% (below 0% with downscale protec-
tion) due to burnout protection function.  Check leadwires
in such a case.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibra-
tion.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.

EXTERNAL DIMENSIONS  

mm (inch)

■ 

TERMINAL ASSIGNMENT

130 (5.12)

3 (.12)

50 (1.97)

82 (3.23)

2–4.3 (.17) dia.

MTG HOLE

TERMINAL COVER

7–M3.5 SCREW

8 (.31)

91 (3.58)

99 (3.90 )

25 (.98)

1

2

3

5

6

7

8

■ 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient
accuracy level.  Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure

1) – 3).

5) Go through the same procedure for Output 2.  Extender

Card (model: 10EC) is required to access the Output 2
Adjustments on top of the unit maintaining electrical
connection at the rear connector.

MAINTENANCE

Regular calibration procedure is explained below:

■ 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%,
50%, 75% and 100% input signal.  Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of
tolerance, recalibrate the unit according to the "ADJUST-
MENT PROCEDURE" explained earlier.

1

2

5

6

7

8

CJC SENSOR

(model: CJM)

*

Deleted with Option /N

*

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty.  To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

Reviews: