PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for 
Model PU-2x (EM-9255), Section A.

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

01

S

MAINTENANCE SWITCH (lock command)

0

MTSW: MON.MODE

MONITOR mode: data monitoring only

1

MTSW: PRG.MODE

PROGRAM mode: “P” marked data modifiable

02

P

Alphabets & No.

TG: XXXXXXXXXX

Tag name entry (10 characters max.)

03
04

P

D

Number (%)
No input

OUTPER XXX.XX
OUTTMP XXXXXX

Output status monitor (%) & simulation output
Output temperature monitor *

1

06

D

No input

INPVAL XXXXXX

Input status monitor in Ω.

10

TYPE OF RTD

P
P

31
32

RB-1: Pt 100
RB-2: JPt 100

Pt 100 (JIS ’89)
JPt 100 (JIS ’89)

D
D

33
34

RB-3: Pt 50
RB-4: Ni 508.4

Pt 50 Ω (JIS ’81)
Ni 508.4 Ω

P

36

RB-6: Pt 100_97

Pt 100 (JIS ’97, IEC)

14
15

P
P

Actual value
Actual value

SCLLOW XXXXXX
SCLHIG XXXXXX

Input range scaling 0% value
Input range scaling 100% value
Use the same temp. unit as selected in ITEM 21.

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%). 
When data is entered, output (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).
When data is entered, output (%) is shown.

21

P

TEMPERATURE SCALE

0
1
2

TMPSCL: [°C]
TMPSCL: [°F]
TMPSCL: [K]

Program ITEM 21 first before ITEM 14 when °F or K calibration 
is needed.  This procedure is necessary whenever thermocouple 
type is changed.

Modification Code

D: No modification (writing) possible. Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

*1. Temperature is indicated in the unit selected in ITEM 21.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.