INSTRUCTION FOR INSTALLATION AND USE - LUNA 550V - 550DV - 850V - 850DV GOLD - GAS
M-DESIGN
12
Fig. 5 ROOF EXIT with 90° bends
CAUTION :
if the vertical lenght is over 3 meter longer than the horizontal lenght, you will
need to place a reduction ring of
Ø 60.
Appliance
Ø 150/100 and Ø 200/130
850 V / 850 DV
550 V / 550 DV
for each 90° bend substract 1 m horizontaly or add 1 m verticaly.
850 V / 850 DV
550 V / 550 DV
for each 45° / 30° / 15° bend substract 0,5 m horizontaly or add 0,5 m
verticaly.
FIG. 5
Ø 150/100 with reduction USVK13 on the appliance
Appliance
A (min)
B (max)
C (min)
(A+B+C ) max
850 V / 550 V
1,25 m
A+C
B-A
16m
850 DV / 850 DV
1,25 m
A+C+0,5
B-A-0,5
15m
Ø 200 / 130
Appliance
A (min)
B (max)
C (min)
(A+B+C) max
850 V / 550 V
1,25 m
(A+C) + 7m
B-A -9m
20m
850 DV / 550 DV
1,25 m
(A+C) + 6m
B-A-8m
19m
Fig. 5 ROOF EXIT with 90° bends