SEDONA BY LYNX™ VENT HOOD CARE & USE/INSTALLATION
|
7
ELECTRICAL CONNECTIONS
• The following are Manufacturer’s Suggestions. Always Observe Local Building Codes.
Hoods installed in custom canopies constructed of combustible materials should be installed with the
combustible material structure a minimum of 36” above the cooking surface. Hoods installed in custom
canopies constructed of non-combustible materials, should be installed with the non-combustible material
structure a minimum of 30” above the cooking surface. Follow all instructions regarding minimum safe clearances
and installation location. Failure to do so may result in a safety hazard or fire. To reduce the risk of fire use only
metal ductwork.
WARNING
Ensure that the power supply is disconnected before proceeding. Verify that the power supply matches the ratings
found on the appliance data label before proceeding. The complete appliance must be properly grounded at all times
when electrical power is applied. Do not ground the appliance with the neutral (white) house supply wire. A separate
ground wire must be utilized. Failure to complete electrical connections properly may result in damaged or
non-functional systems. Follow instructions carefully to ensure proper installation.
It is the owner’s responsibility to ensure that a qualified person performs the electrical connection of this
appliance. The electrical installation, including minimum supply wire size, must comply with the National Electric
Code ANSI/NFPA 70-1990 (or latest revision) and local codes and ordinances. A copy of this standard may be
obtained from:
National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 02169-7471
Important Electrical Requirements:
Observe all National and local governing codes and ordinances. Have all
electrical installation done by a qualified electrical installer. This Hood requires a 120 Volt, 60 Hertz electrical supply of
an individual properly grounded branch circuit protected by a 15 or 20 Amp circuit breaker.
The Sedona by Lynx™ Vent Hood is supplied with a 6.0 Amp three speed fan control.
For safety precautions, each Ventilation Hood should be installed in a GFCI protected branch circuit.
WIRE CONNECTIONS
There are 3 wires on the front panel that require
connection.
BLACK 120 VAC from electrical panel (usually black)
WHITE Neutral from electrical panel (white)
GREEN Ground from electrical panel (usually green)
CAUTION: The neutral wire (white) must only be
connected to the white neutral wire coming in
from the electrical panel.
Hood
House Electrical
Panel
Green or bare wire
White
(N)
120V Black (L)