Luxaire Climasure PAC024 Technical Manual Download Page 5

246836-LTG-E-0107

Unitary Products Group

5

6.

Unit shall be built on a formed, "Super-Structure" design 
base pan, with embossments at critical points to add 
strength, rigidity and aid in minimizing sound.

7.

Full perimeter base rails shall be provided to assure 
reliable transit of equipment.

8.

Condensate pan shall be internally sloped and conform to 
ASHARE 62-89 self-draining standards, with 3/4" NPTI 
copper, ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

1.

Fan shall be direct drive, constant torque design with 5 
available speed selections.

2.

Fan wheel shall be double-inlet type with forward-curved 
blades, dynamically balanced to operate smoothly 
throughout the entire range of operation. Airflow design 
shall be constant air volume.

3.

Bearings shall be sealed and permanently lubricated for 
longer life and no maintenance.

4.

Fan assembly shall be accessible via removable inlet ring.

OUTDOOR (CONDENSER) FAN ASSEMBLY

1.

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to 
corrosion resistant steel spider bracket and shall be 
statically balanced for smooth operation.

2.

The outdoor fan motor shall be totally enclosed with 
permanently lubricated bearings and internally protected 
against overload conditions.

REFRIGERANT COMPONENTS

Compressors:

a. Shall be fully hermetic reciprocating, rotary or scroll type, 

direct drive, internally protected with internal high-
pressure relief and over temperature protection. The 
hermetic motor shall be suction gas cooled and have a 
voltage range of + or - 10% of the unit nameplate 
voltage.

b. Shall have internal isolation and sound muffling to 

minimize vibration and noise, and be externally isolated 
on a dedicated, independent mounting.

Coils:

a. Evaporator and condenser coils shall have aluminum 

plate fins mechanically bonded to seamless internally-
enhanced copper tubes with all joints brazed.

b. Evaporator and Condenser coils shall be of the direct 

expansion, draw-thru design.

Refrigerant Circuit and Refrigerant Safety Components shall 
include:

a. Independent fixed-orifice or TXV expansion devices.

b. Filter/strainer to eliminate any foreign matter.

c. Accessible service gage connections on both suction 

and discharge lines to charge, evacuate, and measure 
refrigerant pressure during any necessary servicing or 
troubleshooting, without losing charge and without 
disrupting condenser or evaporator air flow.

Unit Controls:

a. Controls shall be mounted in a large control box, allowing 

easy access for trouble shooting and maintenance 
without affecting the normal system operation pressures.

b. Unit shall have large, easily removable panels, covering 

electrical controls and compressor, allowing easy access 
for any necessary maintenance or servicing.

ELECTRIC HEATING SECTION

1.

An electric heating section, with nickel chromium elements, 
shall be provided in a range of 5 thru 15 KW, single phase 
only.

2.

The heating section shall have a primary limit control(s) 
and automatic reset, to prevent the heating element 
system from operating at an excessive temperature.

3.

The heating section assembly shall slide out of the unit for 
easy maintenance and service.

UNIT OPERATING CHARACTERISITCS

1.

Unit shall be capable of starting and running at 125° F 
outdoor temperature, exceeding maximum load criteria of 
ARI Standard 210/240.

2.

The compressor, with standard controls, shall be capable 
of cooling operation down to 45° F outdoor temperature. 
Accessory low ambient kit shall be available for operation 
to 0° F.

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location.

Separate openings shall be provided for the control wiring.

Summary of Contents for Climasure PAC024

Page 1: ...ng air conditioners are designed for outdoor installation Only utility and duct connections are required at the point of installation Field installed electric heater accessories are available to provi...

Page 2: ...Sound Performance 27 Electrical Data 27 Weights and Dimensions 35 Component Location Cooling Unit and Heat Pump LUHFW ULYH RQGHQVHU DQ 0RWRU HFRUDWLYH 3URWHFWLYH RLO XDUG HDY DXJH DVH 5DLOV RQWURO R...

Page 3: ...nd gas system safeties are monitored and recorded by the system to insure unit performance Equal size side supply and return duct connections allows easy hook up of ducts to match low crawl spaces wit...

Page 4: ...mpressor if undesirable operating conditions occur Pressure Switches High pressure switches standard in all heat pump units When abnormal conditions are sensed through the pressure switches the unit w...

Page 5: ...unting Coils a Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed b Evaporator and Condenser coils sh...

Page 6: ...11 3 16 0 16 0 Rows 2 2 2 2 2 2 Fins per inch 15 15 15 15 15 15 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined EVAPORAT...

Page 7: ...ecip Recip Recip Recip Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 28 11 28 11 28 16 16 16 Rows 2 2 2 2 2 2 Fins per inch 15 15 15 15 15 15 Tube diameter in 3 8 3 8 3 8 3...

Page 8: ...024 2 0 PAC PHP 208 230 1 60 187 252 125 030 2 5 PAC PHP 208 230 1 60 187 252 125 036 3 0 PAC PHP 208 230 1 60 187 252 125 208 230 3 60 187 252 125 042 3 5 PAC PHP 208 230 1 60 187 252 125 048 4 0 PA...

Page 9: ...0 9 8 8 21 7 1 9 16 0 14 0 12 0 10 0 7 9 67 23 1 1 8 20 5 18 5 16 5 14 4 12 4 10 4 8 4 19 8 1 9 18 5 17 2 15 4 13 4 11 4 9 3 7 3 62 21 7 1 8 21 7 21 0 19 6 17 6 15 6 13 5 11 5 18 7 1 9 18 7 18 4 18 0...

Page 10: ...9 4 67 27 4 2 2 25 0 22 5 19 9 17 4 14 9 12 3 9 8 24 3 2 5 23 0 21 1 18 6 16 1 13 6 11 0 8 5 62 25 7 2 2 25 7 25 3 23 9 21 4 18 8 16 3 13 8 23 0 2 5 23 0 22 8 21 8 19 3 16 8 14 2 11 7 57 25 7 2 2 25 7...

Page 11: ...4 24 3 21 3 18 3 15 3 12 2 31 9 3 0 28 7 26 1 23 1 20 1 17 0 14 0 11 0 62 33 7 2 7 33 4 32 1 29 4 26 4 23 3 20 3 17 3 30 4 3 0 30 3 29 5 27 4 24 4 21 4 18 3 15 3 57 33 7 2 7 33 4 32 1 29 4 26 4 23 3...

Page 12: ...0 28 4 24 9 21 4 17 8 14 3 36 7 3 4 33 1 29 9 26 4 22 8 19 3 15 8 12 2 62 38 6 3 1 38 5 37 0 34 1 30 6 27 0 23 5 20 0 34 9 3 3 34 9 33 7 31 0 27 5 24 0 20 4 16 9 57 38 6 3 1 38 5 37 0 34 1 30 6 27 0...

Page 13: ...8 26 7 22 7 18 7 14 6 42 0 3 7 37 1 33 2 29 1 25 1 21 1 17 0 13 0 62 44 1 3 4 43 0 41 0 36 9 32 9 28 8 24 8 20 8 40 4 3 7 39 8 37 9 34 1 30 1 26 0 22 0 17 9 57 44 1 3 4 43 0 41 0 36 9 32 9 28 8 24 8...

Page 14: ...35 9 30 8 25 7 20 7 15 6 54 8 4 6 45 8 40 8 35 7 30 7 25 6 20 6 15 5 62 66 1 4 3 33 0 27 9 22 9 17 8 12 8 7 7 2 7 57 5 4 6 40 5 36 8 31 7 26 7 21 6 16 6 11 5 57 59 4 4 1 46 0 40 9 35 9 30 8 25 7 20 7...

Page 15: ...13 1 11 1 9 0 67 24 5 1 9 22 0 19 9 17 9 15 9 13 9 11 9 9 8 21 6 2 0 20 3 18 9 17 0 15 0 12 9 10 9 8 9 62 23 3 1 9 23 3 22 7 21 5 19 5 17 5 15 4 13 4 20 9 2 0 20 9 20 6 19 9 17 9 15 8 13 8 11 8 57 23...

Page 16: ...17 5 15 0 12 5 9 9 7 4 67 25 4 2 0 22 2 19 7 17 2 14 7 12 1 9 6 7 1 22 8 2 2 20 7 18 6 16 0 13 5 11 0 8 5 5 9 62 26 0 2 1 25 2 23 6 21 1 18 5 16 0 13 5 11 0 23 1 2 2 22 7 21 4 19 0 16 5 14 0 11 4 8 9...

Page 17: ...24 5 21 4 18 4 15 4 12 3 31 2 3 2 28 7 26 3 23 3 20 3 17 2 14 2 11 2 62 33 4 2 9 32 8 31 3 28 2 25 2 22 2 19 1 16 1 30 1 3 1 29 8 28 8 26 4 23 4 20 4 17 3 14 3 57 33 4 2 9 32 8 31 3 28 2 25 2 22 2 19...

Page 18: ...26 9 23 3 19 8 16 2 39 9 3 6 35 6 32 4 28 9 25 3 21 8 18 3 14 7 62 42 3 3 3 41 1 38 6 35 1 31 6 28 0 24 5 20 9 39 3 3 6 38 2 36 2 32 7 29 1 25 6 22 1 18 5 57 42 3 3 3 41 1 38 6 35 1 31 6 28 0 24 5 20...

Page 19: ...29 5 25 4 21 4 17 4 45 2 4 1 40 3 36 6 32 5 28 5 24 4 20 4 16 4 62 46 9 3 5 44 5 41 4 37 4 33 3 29 3 25 2 21 2 45 4 4 1 42 8 39 9 35 9 31 8 27 8 23 7 19 7 57 46 9 3 5 44 5 41 4 37 4 33 3 29 3 25 2 21...

Page 20: ...6 36 6 31 5 26 5 21 4 52 5 4 9 47 8 44 1 39 0 34 0 28 9 23 9 18 8 62 63 6 4 5 55 0 50 0 44 9 39 8 34 8 29 7 24 7 54 5 5 0 49 4 45 7 40 6 35 6 30 5 25 5 20 4 57 63 6 4 5 55 0 50 0 44 9 39 8 34 8 29 7...

Page 21: ...66 1 76 1 86 1 97 2 07 2 17 2 27 2 37 1000 55 MBH 10 56 12 31 14 45 17 07 20 27 24 17 28 94 34 76 KW 1 30 1 40 1 50 1 60 1 70 1 80 1 91 2 01 70 MBH 7 93 9 69 11 83 14 45 17 65 21 55 26 32 32 14 KW 1...

Page 22: ...03 3 17 3 30 70 MBH 16 15 19 13 22 65 26 83 31 77 37 62 44 56 52 77 KW 2 94 3 08 3 21 3 34 3 48 3 61 3 75 3 88 80 MBH 14 15 17 13 20 65 24 82 29 77 35 62 42 56 50 77 KW 3 23 3 36 3 50 3 63 3 76 3 90...

Page 23: ...4 236 910 878 251 980 821 269 1053 751 281 1125 Medium 1166 306 912 1101 323 977 1037 338 1042 977 351 1102 833 321 1139 Medium High 1255 385 971 1169 400 1030 1109 412 1087 996 384 1123 841 328 1146...

Page 24: ...0 09 700 0 08 0 08 0 08 0 09 0 10 800 0 09 0 09 0 09 0 10 0 12 900 0 1 0 10 0 10 0 11 0 13 1000 0 12 0 12 0 12 0 13 0 15 1100 0 13 0 13 0 13 0 14 0 17 1200 0 15 0 15 0 15 0 16 0 19 1300 0 17 0 17 0 17...

Page 25: ...0 38 0 41 2100 0 39 0 39 0 39 0 40 0 43 2200 0 41 0 41 0 41 0 42 0 45 060 5 0 PAC 800 0 09 0 09 0 09 0 10 0 12 900 0 1 0 10 0 10 0 11 0 13 1000 0 12 0 12 0 12 0 13 0 15 1100 0 13 0 13 0 13 0 14 0 17 1...

Page 26: ...0 1160 PHP 1300 1300 1270 1270 060 5 0 PAC 208 230 1 60 1300 1300 1270 1160 PHP 1300 1300 1270 1270 Indoor Blower Specifications Size Tons Model Motor HP RPM Eff SF Frame 024 2 0 PAC PHP 1 2 1100 0 8...

Page 27: ...1 7 59 7 69 8 79 8 70 80 030 2 5 208 230 1 60 10 6 61 0 16 5 1 1 4 1 None 19 8 25 2PH08510506 3 6 4 8 1 17 2 19 9 26 7 30 0 30 30 2PH08510706 4 9 6 5 1 23 5 27 1 34 5 39 0 35 40 2PH08511006 7 2 9 6 1...

Page 28: ...19 9 44 0 47 3 50 50 2PH08510706 4 9 6 5 1 23 5 27 1 51 8 56 3 60 60 2PH08511006 7 2 9 6 1 34 5 39 8 65 6 72 2 70 80 2PH08511506 10 8 14 3 1 51 7 59 7 87 1 97 1 90 100 208 230 3 60 8 2 72 0 16 0 1 6...

Page 29: ...246836 LTG E 0107 Unitary Products Group 29 PAC PHP024 060 Typical Wiring Diagrams PAC024 060 Typical Cooling Unit 208 230 1 60 volt Wiring Diagram...

Page 30: ...246836 LTG E 0107 30 Unitary Products Group PAC036 048 and 060 Typical Cooling Unit 208 230 3 60 volt Wiring Diagram...

Page 31: ...246836 LTG E 0107 Unitary Products Group 31 PAC048 060 Typical Cooling Unit 460 3 60 volt Wiring Diagram...

Page 32: ...246836 LTG E 0107 32 Unitary Products Group PHP024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 33: ...246836 LTG E 0107 Unitary Products Group 33 PHP036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram...

Page 34: ...246836 LTG E 0107 34 Unitary Products Group PHP060 Typical Heat Pump 460 3 60 volt Wiring Diagram...

Page 35: ...9 70 PHP 345 342 21 75 14 79 71 91 101 030 2 5 PAC 273 270 21 75 14 63 62 71 73 PHP 350 347 21 75 14 80 72 92 103 036 3 0 PAC 348 345 23 5 15 79 83 94 90 PHP 353 350 23 5 15 80 84 95 91 042 3 5 PAC 35...

Page 36: ...3 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 PHP 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 042 3 5 PAC 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 PHP 32 13 16 34 11 1...

Page 37: ...n Distance in Direction Distance in Top1 1 Units must be installed outdoors Over hanging structure or shrubs should not obscure condenser air discharge outlet 60 Right 24 Front 36 Left 24 Rear2 2 Unit...

Page 38: ...246836 LTG E 0107 38 Unitary Products Group...

Page 39: ...246836 LTG E 0107 Unitary Products Group 39...

Page 40: ...t to change without notice Printed in U S A 246836 LTG E 0107 Copyright 2007 by Unitary Products Group All rights reserved Supersedes 246836 LTG D 1206 Unitary 5005 Norman Products York OK Group Drive...

Reviews: