25
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per
degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
AL6B060F3(C)
INDOOR COIL MODEL NO.
FC64D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1500
1700
1900
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
54.9
58.0
53.0
59.0
63.9
56.8
58.9
54.4
60.1
66.6
58.6
59.7
55.7
61.3
69.3
S.C.
52.0
45.1
39.2
37.3
30.2
53.5
48.2
41.0
39.5
31.8
55.1
51.2
42.7
41.8
33.5
KW
3.02
3.04
3.03
3.06
3.09
3.11
3.12
3.11
3.14
3.18
3.20
3.21
3.19
3.22
3.26
75
T.C.
51.9
54.9
50.7
56.5
61.7
53.8
55.7
52.1
57.9
63.5
55.8
56.4
53.5
59.3
65.4
S.C.
49.2
44.2
37.9
36.5
29.4
50.9
47.1
39.9
38.8
30.9
52.6
50.0
41.9
41.1
32.4
KW
3.41
3.43
3.43
3.44
3.47
3.50
3.51
3.50
3.52
3.55
3.58
3.59
3.58
3.60
3.64
85
T.C.
48.8
51.7
48.4
54.0
59.4
50.8
52.4
49.8
55.7
60.5
52.9
53.1
51.2
57.4
61.6
S.C.
46.4
43.3
36.7
35.8
28.6
48.3
46.0
38.9
38.1
30.0
50.2
48.7
41.1
40.4
31.4
KW
3.80
3.82
3.82
3.82
3.84
3.88
3.90
3.90
3.90
3.92
3.96
3.97
3.97
3.98
4.01
95
T.C.
45.7
48.6
46.1
51.5
57.2
47.8
49.2
47.5
53.5
57.4
50.0
49.8
49.0
55.5
57.7
S.C.
43.6
42.4
35.5
35.1
27.8
45.6
44.9
37.9
37.4
29.1
47.7
47.5
40.2
39.7
30.3
KW
4.19
4.21
4.22
4.20
4.22
4.27
4.28
4.29
4.28
4.30
4.35
4.35
4.36
4.36
4.38
105
T.C.
43.8
44.8
43.5
48.9
54.7
45.7
45.4
44.9
50.5
55.3
47.5
46.1
46.4
52.2
55.9
S.C.
41.7
40.1
33.7
33.8
26.4
43.5
42.0
36.2
36.0
27.7
45.3
44.0
38.6
38.2
29.0
KW
4.84
4.87
4.89
4.85
4.85
4.91
4.92
4.96
4.92
4.93
4.97
4.98
5.02
4.99
5.00
115
T.C.
42.0
41.1
41.0
46.4
52.3
43.6
41.8
42.4
47.7
53.3
45.2
42.5
43.8
48.9
54.2
S.C.
39.9
37.9
32.0
32.6
25.1
41.5
39.2
34.5
34.7
26.4
43.1
40.5
37.0
36.8
27.7
KW
5.47
5.51
5.54
5.47
5.47
5.52
5.55
5.60
5.54
5.54
5.58
5.58
5.66
5.61
5.61
125
T.C.
40.2
37.4
38.5
43.9
49.9
41.5
38.1
39.9
44.8
51.2
42.8
38.9
41.3
45.7
52.5
S.C.
38.1
35.7
30.3
31.4
23.8
39.5
36.4
32.8
33.4
25.1
40.8
37.1
35.3
35.4
26.4
KW
6.10
6.15
6.20
6.10
6.08
6.14
6.17
6.25
6.16
6.15
6.18
6.19
6.30
6.22
6.21
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
AHE60D
–
1.00
1.02
0.96
AHR60D
–
0.97
0.97
1.01
AV*60
–
0.98
0.97
0.96
AHX60
–
1.00
1.03
0.96
F6FP060
–
1.00
1.03
0.96
MV20D
FC/MC60D
0.99
1.00
0.97
MV20D
FC/MC62D
1.00
1.02
0.98
MV20D
FC64D
1.02
1.04
0.94
MX20D
FC/MC60D
0.99
1.00
0.95
MX20D
FC/MC62D
1.01
1.03
0.95
MX20D
FC64D
1.03
1.07
0.95
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*C20
FC/PC60C
0.97
0.94
0.95
T*9X*C20
FC/PC60C
0.97
0.95
0.95
T*9X*D20
FC/MC/PC60D
0.98
0.97
0.94
T*(8,L)X*C20
FC/MC/PC60D
0.97
0.96
0.93
T*9X*C20
FC/MC/PC60D
0.97
0.95
0.95
T*(8,L)X*C20
FC/MC62D
0.99
0.99
0.93
T*9X*C20
FC/MC62D
0.99
0.99
0.95
T*9X*D20
FC/MC62D
0.99
0.98
0.95
T*(8,L)X*C20
FC64D
1.02
1.03
0.96
T*9X*D20
FC64D
1.01
1.02
0.95
(L*LC/T*8V/T*LV)*C20
FC/MC62D
0.98
0.97
0.98
(L*9C/T*9V)*C20
FC/MC62D
0.98
0.97
0.98
(L*9C/T*9V)*D20
FC/MC62D
0.98
0.97
0.96
(L*LC/T*8V/T*LV)*C20
FC64D
1.02
1.04
1.00
(L*9C/T*9V)*C20
FC64D
1.01
1.01
0.99
(L*9C/T*9V)*D20
FC64D
1.01
1.01
0.99