TEMPERATURE SWING:

The amount of temperature variation between load-on and load-off is changed by adjusting the

swing setting.  The default value for this thermostat is #4, and the adjustment range is from #1 to #9.  A smaller swing
number makes the temperature control more precise and constant, and increases the number of cycles per hour.  A larger
swing number will produce a greater variation between load-on and load-off events, and decreases the number of cycles
per hour.

To adjust the Swing setting: Set the thermostat to OFF mode using the System Mode switch, and hold down the SAVE
button for at least 5 seconds.  When the screen changes to a single digit, this is the current Swing setting value and it
can be adjusted using the UP or DOWN buttons.  The thermostat will return back to the normal Run mode screen if no
buttons are pressed for 4 seconds.

TEMPERATURE CALIBRATION:

This thermostat is accurately calibrated at the factory, and in most cases alteration to this

setting should not be required.  The Calibration feature allows you to manually offset the room temperature measurement
by as much as plus or minus 5°F (3°C) degrees from its original value.  0°F (0°C) is the default setting.

To adjust the Calibration setting: Set the thermostat to OFF mode using the System Mode switch, press both the UP and
DOWN together for at least 2 seconds.  When the screen changes to a single digit, this is the current Calibration setting
value and it can be adjusted using the UP or DOWN buttons.  The thermostat will return back to the normal Run mode
screen if no buttons are pressed for 4 seconds.

This thermostat is powered by two “AA” Alkaline batteries. The batteries should be replaced AT LEAST once per year (or
sooner, if the “LOW BAT” battery symbol appears in the display screen).  When the LO BAT symbol is shown, the
temperature digits will also display the word “Lo”.   The batteries are located on the back of the circuit board, and can be
accessed by pulling the front portion of the thermostat straight outwards and removing it from the wall. When installing
new batteries, we recommend using only brand new Energizer

®

or DURACELL

®

, “AA” size alkaline batteries.  Please

observe the polarity markings shown in the battery compartment to ensure proper installation.  When finished, line up the
front of the thermostat to the base, and firmly press together.

ADVANCED FEATURES:

BATTERY REPLACEMENT:

Summary of Contents for DMH110b

Page 1: ... WARNING Use Energizer or DURACELL Alkaline Batteries Only Energizer is a registered trademark of Eveready Battery Company Inc DURACELL is a registered trademark of The Procter Gamble Company LUX Products Corporation Mt Laurel New Jersey 08054 http www luxproducts com SYSTEM COMPATIBILITY 1 Stage Heat 1 Stage Cool Electronic Accuracy Innovative SAVE Feature Gas Elec Fan Option Battery Powered Only...

Page 2: ...ally left open 3 Do not locate the thermostat where unusual heating or cooling conditions may be present such as direct sunlight above a lamp television or radiator or on a wall next to an exterior door or window 4 Do not locate in a damp environment as this can lead to corrosion that may shorten thermostat life 5 If painting or construction work is still ongoing cover the thermostat completely or...

Page 3: ... heat and oil heat OPEN Heat Pump Use this setting if you have a heat pump unit which looks just like an outside air conditioning unit but is used for both cooing and heating JP2 DELAY CLOSED 5 Minutes default This setting changes the length of time that the system must remain either on or off before it will switch to the alternate on or off state The main purpose of this setting is to provide equ...

Page 4: ... 5F 3 C degrees while in Heat mode or raise the set temperature by 5 F 3 C degrees while in Cool mode When you leave the house simply press the SAVE button one time to put the thermostat into Save mode and the word SAVE will be shown on the screen When you return home press the SAVE button again to cancel the Save mode and return back to the previous set temperature that you were using originally ...

Page 5: ...ent by as much as plus or minus 5 F 3 C degrees from its original value 0 F 0 C is the default setting To adjust the Calibration setting Set the thermostat to OFF mode using the System Mode switch press both the UP and DOWN together for at least 2 seconds When the screen changes to a single digit this is the current Calibration setting value and it can be adjusted using the UP or DOWN buttons The ...

Page 6: ...m the date of original purchase Some states do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you Please return malfunctioning or defective units to the location from which the purchase was made along with proof of purchase Please refer to TECHNICAL ASSISTANCE before returning thermostat Purchaser assumes all risks and liability for incidental ...

Page 7: ...mostat location they are located with your heating and cooling equipment 4 For Heat Pumps use the B or O wire NOT BOTH Typically neither are used in a conventional system 5 If Y and C wires are both present then C is a common wire 6 If you have a B wire in your system which is used as a common wire connecting it to the B terminal on this thermostat may damage your system and or the thermostat W1 4...

Page 8: ...AGE COOLING WITH TWO SEPARATE 24V TRANSFORMERS Factory RH RC Jumper Wire REMOVED FAN COMMON HEATER AIR CONDITIONER 5 6 WIRES BLACK TERMINAL LETTERS ARE TYPICAL GRAY TERMINAL LETTERS ARE BRAND SPECIFIC 24V HEAT POWER 24V COOL POWER 5 X C F G FAN O B Use O or B Terminals Never Both RC V R Y1 6 Y G Y O B W RH RC SINGLE STAGE HEAT PUMP SYSTEM WITH NO AUX OR EMERGENCY HEAT Factory RH RC Jumper Wire 24V...

Reviews: