Air heater unit ATD (A, G)
GB
8
Operating data
Max air temperature around the motor:
+40°C.
Min air temperature around the motor:
-15°C.
ATDA:
Max permitted operating pressure:
1.6 MPa at 100˚C
All heat exchangers are leak-tested under water using dry air.
ATDG:
Max permitted operating pressure:
1.0 MPa at 150˚C
Test pressure:
1.3 MPa
The pH value of the steam must not drop below 8.5 and
should normally be 9.5. The oxygen content must not
exceed 0.01 mg/l.
Motor data
For information, refer to the air heater unit’s data plate.
Weight and volume
For information about the air heater unit’s dry weight and
fluid volume, refer to the air heater unit’s data plate.
Heat exchanger
The heat exchanger consists of tubes that are mechanic-
ally expanded onto the fins. The fins are manufactured
as whole plates without slots to avoid dust and fibres
collecting on the fin structure.
Fan unit
The fan unit’s motor is an outer rotor motor, journalled on
ball bearings, with a self-resetting thermal cut-out (not
size 44-3). The fan blades are made of pressed galvanised
sheet steel or aluminium. The fan unit is coated with a
black surface finish.
Table 4. Technical data, fan unit
ATD
(A,G)
Rota-
tional
speed
(rpm)
Rated
output
(kW)
Rated current (A), 50 Hz
Protec-
tion
cut-out
Protec-
tion
class
1-phase
230 V
3-phase
400 V
∆
3-phase
400 V
Y
30-1-1
1420
1)
1035
0.11
0.61
-
-
-
-
Yes
IP44
33-1-1
1420
1)
1035
0.11
0.61
-
-
-
-
Yes
IP44
33-1-2
1420
1)
1035
0,11
0.61
-
-
-
-
Yes
IP44
44-1-1
1430
1)
900
0.16
0.81
-
-
-
-
Yes
IP44
44-1-2
1400
1)
0.16
0.81
-
-
Yes
IP44
44-3-1
1430
1)
0.15
-
-
0.64
No
IP44
44-3-2
1430
1)
0.15
-
-
0.64
No
IP44
55-1-1
935
1)
0.29
1.5
-
-
IP54
55-1-2
920
1)
0.29
1.5
-
-
Yes
IP54
55-3-1
1330
1)
1035
0.65
0.46
-
-
1.2
-
-
0.79
Yes
IP54
55-3-2
1330
1)
1035
0.65
0.46
-
-
-
-
-
-
Yes
IP54
66-1-1
900
1)
0.37
1.7
-
-
Yes
IP54
66-3-1
1360
1)
0.84
-
1.65
-
Yes
IP54
1)
Speed as delivered. Other speeds can be obtained by altering the motor
connections as indicated in the connection diagram, see Figures 15–22.
Table 5. Speed with accessories for transformer control.
ATD (A,G)
230 V
150 V
130 V
115 V
100 V
80 V
30-1
1420
1)
1190
1035
1)
850
685
1)
500
33-1-1
1420
1)
1190
1035
1)
850
685
1)
500
33-1-2
1360
1)
1160
980
1)
850
680
1)
500
44-1-1
1430
1)
1210
900
1)
660
1)
550
410
44-1-2
1400
1)
1030
1)
750
1)
600
500
380
55-1-1
935
1)
670
1)
485
1)
390
310
240
55-1-2
920
1)
420
1)
340
1)
280
240
190
66-1
900
1)
640
1)
505
1)
430
355
270
1)
Speed as delivered
Protection classes
For information, refer to Table 4.
Technical data