Electrical installation
Description of connection sockets
29
© Lutz-Jesco GmbH 2014
Subject to technical changes.
140327
Solenoid-Diaphragm Dosing Pump
MAGDOS LP
Operating Instructions
BA-10231-02-V03
9.2.1 Connection socket 1
9.2.1.1 Stroke feedback output
At the stroke feedback output, the dosing pump reports back each
executed stroke to the pulse input of another dosing pump. In this way,
it is possible to network several dosing pumps and to trigger synchro-
nized dosing strokes.
Fig. 9-2: Synchronization of several dosing pumps by means of stroke feedback and pulse
control
Optocoupler, max. 30 V DC, 5 mA
Assignment of pin 1, 2
9.2.1.2 Release input
Using the Release input, it is possible to start or stop the dosing pump
externally.
Potential-free contact
Programmable NC or NO contact
Assignment of pin 3, 4
* Applies to cable colours of cables from Lutz-Jesco GmbH. No liability
is accepted for cables from other manufacturers.
9.2.2 Connection socket 2
9.2.2.1 Analog input
The analog input makes it possible to control the delivery capacity by
means of a 0/4 - 20 mA signal. The delivery capacity is regulated via the
stroke frequency.
0/4 - 20 mA Signal
Invertible
Current range variable
Working resistance: 150 Ohm
For information on setting the
Analog input
operating mode, see
9.2.2.2 Pulse input
The pulse input makes it possible to control the delivery capacity by
means of pulses. The system regulates the delivery capacity by means
of the dosing pump's stroke frequency and number of strokes in
dependence on the number of pulses and the pulse spacing.
Provided potential-free contact
For potential-free NO contact, e.g. a contact-type water meter
5 V DC supply voltage (current across all connections limited to a
total maximum of 50 mA)
Pulse length min. 4 ms
For information on setting the
Pulse input
operating mode, see
* Applies to cable colours of cables from Lutz-Jesco GmbH. No liability
is accepted for cables from other manufacturers.
Pin
M12x1
(A-coded)
Assignments
Connection
Cable colour*
1
Optocoupler
collector (+)
Brown
BN
2
Optocoupler
emitter (-)
White
WH
3
Ground (GND)
Blue
BU
4
External On/Off
Black
BK
Table 9-3: Connection socket 1
1
2
3
4
Pin
M12x1
(A-coded)
Assignments
Connection
Cable colour*
1
Pulses
Pulse input:
Analog input:
Brown
BN
2
(+) 0/4 - 20 mA
White
WH
3
Ground (GND)
Blue
BU
4
-
+ 5 V DC
-
Black
BK
Table 9-4: Connection socket 2
1
3
3
2