Installation
Installation location
15
© Lutz-Jesco GmbH 2016
Subject to technical changes.
160520
BA-20901-02-V01
Chlorinator C 2526
Operating instructions
7 Installation
DANGER!
Danger to life from chlorine poisoning!
Chlorinators without gas warning devices are an increased safety risk,
since it is not possible to detect escaping chlorine gas in good time or
at all.
ð
Install a gas warning device.
WARNING!!
Increased risk of accidents due to insufficient qualifica-
tion of personnel!
Chlorinators and their accessories must only be installed, operated
and maintained by personnel with sufficient qualifications. Insufficient
qualification will increase the risk of accidents.
ð
Ensure that all action is taken only by personnel with sufficient and
corresponding qualifications.
ð
Prevent access to the system for unauthorised persons.
Note
Damage to the system due to incorrect installation
The failure to observe installation instructions (e.g. use of unsuitable
tools, incorrect torque) can damage the system parts.
ð
Use suitable tools.
ð
Note the specified torque.
7.1 Installation location
The dosing device is usually installed together with the injectors in the
dosing device room. We do not recommend installation in the same room
as the chlorine gas supply.
The room must fulfil the following requirements:
n
secured against access by unauthorised persons,
n
protected against weather conditions,
n
frost-free,
n
permissible ambient temperature adhered to (see Section 5
"Technical data" on page 13),
n
room of sufficient size to allow trouble-free assembly as well as
inspection and maintenance of the device at all times,
n
an electrical connection is given,
n
the room can be ventilated well,
n
the room must comply with the locally valid prescriptions.
Summary of Contents for C 2526
Page 2: ......
Page 46: ...Index 46 Lutz Jesco GmbH 2016 BA 20901 02 V01 Chlorinator C 2526 Operating instructions...
Page 48: ......