PowPak | Installation
Programming without a Vive Hub
Control Module with DALI
Part of the Vive Family
Start Here
Lutron, Pico, and PowPak are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc.
App Store is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license. Android, Google Play and the Google Play logo are trademarks of Google Inc. DALI is a trademark of ZVEI. ©2021 Lutron Electronics Co., Inc.
A
On the PowPak Control Module,
hold
Toggle
button “
u
” for
6 seconds until lights flash.
Both LEDs will begin flashing
twice per second.
Associate Wireless Transmitters to
PowPak Control Module with DALI
Before beginning this step, make sure that there are no
other PowPak modules being set up within the same
building. It is possible that wireless transmitters from other
systems can be incorrectly associated to this module.
1
C
On the PowPak Control Module, hold the
Toggle
button “
u
” for 6 seconds to save association. Lights
will return to high-end and LEDs will stop flashing.
B
Hold the indicated button on each transmitter for
6 seconds. Lights will flash to show that wireless
transmitters have been associated. LEDs also flash
upon successful association.
Test
Link
Cal.
D
Permanently install wireless transmitters
(consult individual component installation guides
for information).
Raise
Lower
Favorite
Set a Favorite Light Level
(Optional)
For Pico remote controls with a
Favorite
Button.
A
Adjust lights to desired level:
Use the
Raise
button “ ” or
Lower
button “ ” on the Pico
remote control.
B
Save favorite level:
Press and hold the
Favorite
button for 6 seconds. The load will
flash 3 times to confirm that the Favorite level is saved.
3
Low-End Trim
A
Enter low-end trim adjustment mode:
Press and hold the
Lower
button “
Δ
” on the fixture control for 12 seconds.
The lights will flash and the bottom LED will begin flashing.
B
Adjust the low-end trim:
Use the
Raise
button “
▲
” and
Lower
button “
Δ
” on the PowPak Control Module to adjust and set
the lights to the desired low-end (0.1 to 45%).
Note:
Low-end depends on the minimum output of connected drivers or ballasts.
C
Save the low-end trim:
Press and hold the
Toggle
button
“
u
”
for 6 seconds to save setting.
The bottom LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A
Enter high-end trim adjustment mode:
Press and hold the
Raise
button “
▲
” on the fixture control for 12 seconds.
The lights will flash and the top LED will begin flashing.
B
Adjust the high-end trim:
Use the
Raise
button “
▲
” and
Lower
button “
Δ
” on the PowPak Control Module to adjust and set
the lights to the desired high-end (55 to 100%).
C
Save the high-end trim:
Press and hold the
Toggle
button
“
u
”
for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
Set Low-End Trim and High-End Trim
(Optional)
For best results, minimize the amount of sunlight entering the
room before performing the following procedures.
Notes
Depending on the fixture manufacturer or load, low-end trim and high-end trim may
need to be adjusted.
• Trim low-end to ensure a stable light level because some loads will flicker or drop out
if trimmed too low.
• Be sure that you can turn on the lights to the low-end trim level without any abnormal
operation.
• The factory default high-end trim is suitable for most applications but can be adjusted
as desired.
4
5
Set Minimum Light Level
(Optional)
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas,
activate Minimum Light Level mode.
A
Enter minimum light level adjustment mode:
Press and hold
Toggle
button “
u
” and
Lower
button “
Δ
” for 12 seconds. Lights will flash
high-low-high and both LEDs will begin flashing.
If lights stop flashing and turn off, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
B
Change the minimum light level:
Press
Raise
button
“
▲
” to set minimum light level to low-end.
Press
Lower
button “
Δ
” to set minimum light level to OFF.
C
Save the minimum light level:
Press and hold
Toggle
button “
u
” for 6 seconds. Both LEDs will quickly flash to indicate that the
new level has been saved.
6
Set Occupancy Light Levels
(Optional)
Note:
Unoccupied light level is always the minimum light level and cannot be adjusted.
A
Set desired occupancy light levels:
Use the
Raise
/
Lower
buttons
“
▲
/
Δ
” on the PowPak Control Modules or the
Raise
/
Lower
buttons “ / ” on associated Pico Remote Controls to adjust lights to the desired level.
Note: Setting lights to OFF during this step will make that control module unaffected by occupancy
(will function as vacancy only).
B
Save occupancy light levels:
Press and hold
Test
button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor
without a
Lights On
button. Release when Sensor lens starts to flash.
Limited Warranty
:
www.lutron.com/en-US/ResourceLibrary/warranty/Limited%20Comm.pdf
Calibrate the Radio Powr Savr Daylight Sensor
Daylight Sensor will control all wired fixtures equally.
A
Press and release the “Cal.” button on the Daylight Sensor.
B
Set lights in room to desired light level.
C
Press and hold the “Cal.” button for 6 seconds.
D
Exit room for 5 minutes to complete calibration.
Note:
When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows
(Optional)
For every row of daylighting a separate PowPak Control Module must be used. For detailed setup
refer to the tuning section of the Radio Powr Savr Daylight Sensor installation guide.
• Select the PowPak Control Module that you want to adjust by pressing the Toggle button.
Test
Link
Cal.
2
Reset Factory Defaults
Note:
In some instances, it may be necessary to reset the
PowPak Control Module with DALI and connected devices
back to factory default settings. Before beginning, make sure
that all devices are connected and powered.
A
Triple-tap the
Toggle
button “
u
” on the PowPak Control
Module and hold until both LEDs begin to flash slowly;
release button.
B
Within 3 seconds of the start of flashing, triple-tap the same
button again and the LEDs will flash rapidly indicating that the
unit has been reset to factory defaults.
Note:
Any associations or programming previously set
up with the PowPak will be erased and will need to be
re-programmed.
Customer Assistance:
India: +91.124.439.0130
Other Countries: +1.610.282.3800
www.lutron.com/support
Customer Assistance www.lutron.com/support
Hereby, Lutron Electronics Co., Inc. declares that the radio equipment type RMNS-DAL32-SZ and RMNS-DAL4-SZ is in
compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the following internet address: www.lutron.com/cedoc