background image

041588 

Rev. A

02/2021

PowPak | Installation

Control Module with DALI

Test

Link

Cal.

+

For each system, ensure that you have:

One PowPak Control Module

At least one Wireless Transmitter

At least one DALI LED Driver or Fluorescent Ballast

Required Components

Radio Powr Savr Occupancy/Vacancy Sensor 

(10 maximum)

Radio Powr Savr Daylight Sensor

(1 maximum)

Pico Remote Control

(10 maximum)

8 mA / 64 mA (based on model) guaranteed for the control lines. 
May be pre-installed in light fixture.

Raise

Toggle

Lower

Top LED

Consult third-party DALI fixtures installation guide for fixture-specific wiring. This device can 

be installed on a fixture / troffer, junction box, or marshalling box using the conduit nut or with 

mounting screws. The device must NOT be mounted inside a fixture / troffer or other metallic 

enclosure. Improper installation can result in degraded wireless communication, intermittent or 

sustained communication failures, and will not be covered under warranty. For mounting and 

wiring best practices see Lutron Application Note #620 (P/N 048620).

+

Occupancy Sensors

Daylight Sensor

Wireless Controls

Occupied:

 

All lights 100%.

Unoccupied:

 

All lights off.

Test

Link

Cal.

All lights dim in response to daylight.

On

All lights 100%

Favorite

All lights 50%

Off

All lights off

Default Functionality

2

 

A

 

Install the 1/2 in NPT to 20 mm conduit adapter (provided) onto the 
PowPak Control Module.

 

B

  The PowPak Control Module can be installed on a fixture / troffer, 

junction box, or marshalling box using the conduit nut (provided) or 
with mounting screws (not provided). Please consult local and national 
electric codes for proper installation.

 

C

  Once installed, energize the PowPak Control Module.

 

D

  Use the 

Toggle

 “ 

u

” , 

Raise 

” and 

Lower

 “

Δ

” buttons to verify  

control wiring. 

English

All Wireless Transmitters must be installed within 9 m 
of the PowPak Control Module with DALI.

DALI Control: 

18 V

-

  

Guaranteed Supply Current:

  8 mA on 4-driver controller (RMNS-DAL4-SZ)

  64 mA on 32-driver controller (RMNS-DAL32-SZ)

Maximum Supply Current: 

250 mA

220 – 240  V

~

  50 / 60 Hz  50 mA

RMNS-DAL4-SZ 
RMNS-DAL32-SZ

 

A

  Connect mains wiring (hot, neutral) to each fixture.

 

B

  Connect DALI control to each fixture.

1

DA+

DA–

NEU

HOT

DALI

MAINS

To additional DALI fixtures

Neutral

Line/Hot

DA+

DA-

+

WARNING! Shock Hazard. 

May result in serious injury or death. Turn off power at circuit 

breaker before installing the unit.

Sample LED 

driver shown

Important Notes: 

Please read before installing.

For installation by a qualified electrician in accordance with all local and 
national electrical codes.

• 

Use copper conductors only.

• 

Check to see that the device type and rating is suitable for the application.

• 

DO NOT

 install if product has any visible damage.

• 

If moisture or condensation is evident, allow the product to dry completely 
before installation.

• 

Operate between 0 °C and 40 °C ambient.

• 

0% to 90% humidity, non-condensing.

• 

For indoor use only.

  Start Here

X

Vive

Programming with a Vive Hub

3

Mount, Wire, and Install DALI Devices and 

Lighting Fixtures

Consult third-party device installation guide

Install PowPak Control Module  

with DALI

Suggested Installation Location: Center of room to 

ensure proper RF coverage of area.

 A 

 Use an iOS or Android compatible device.

 B 

 Download the Lutron Vive app.

 C 

 Open the app and follow the instructions.

 

   Note:

 For further information on set up, programming, and troubleshooting with a Vive 

system, please refer to the installation instructions included with the Vive hub or visit 

www.lutron.com/vive-europe

 

  

Note:

 For programming the PowPak Control Module with DALI without a Vive hub see 

reverse side

.

Customer Assistance   www.lutron.com/support

     

Troubleshooting                                                                                           

www.lutron.com / vive

Ballasts cannot be controlled locally from PowPak Control Module 

with DALI.

•  Ensure that the breaker(s) to the PowPak Control Module are energized.

•  Ensure that the DALI control lines are wired to the lighting fixture(s).

 

Reset to factory defaults.

Lights do not dim as expected.

•  Ensure that DALI control lines are wired properly.

Lights do not respond to Wireless Transmitter(s).

•  Ensure that the breaker(s) to the PowPak Control Module and drivers/ballasts are energized.

•  Ensure that Wireless Transmitters are associated to the PowPak Control Module.

•  Ensure that Wireless Transmitter(s) are within 9 m of the PowPak Control Module.

 

Reset to factory defaults.

Lights are unstable at low-end or flash/flicker at turn-on or turn-off. •  Adjust the low-end trim.

Wireless Transmitter(s) cannot be associated to PowPak Control 

Module with DALI.

•  Ensure that Wireless Transmitter(s) are within 9 m of the PowPak Control Module.

•  The maximum number of Wireless Transmitters have been associated to the PowPak Control Module. To remove a previously set up Wireless Transmitter, tap a 

Wireless Transmitter button three times; on the third tap hold for three seconds and then tap three more times.

Part of the Vive Family

vive.lutron.com

X

DALI to Fixtures

DA+ (Violet)
DA- (Violet/White)

Neutral (Black)

Line / Hot  (Red)

Conduit Nut

1/2 in NPT to  

20 mm Conduit 

Adapter

Wiring a Lever 

Operated Connector

When wiring lever-

operated connectors  

(4 supplied) use  

appropriate gauge solid or 

stranded copper wire. 

1

2

3

10 mm

Lutron Electronics Co., Inc. | 7200 Suter Road

Coopersburg, PA  18036-1299, U.S.A. 

041797 

Rev. A 

02/2021

Bottom  

LED

9 m

maximum

Radio Powr 

Savr Occupancy 

Sensor

Pico  

Remote  

Control

PowPak  

Control Module

Install in center of room  

to maximize RF coverage.

PowPak 

Control 

Module

Wire Gauge

Total DALI-compliant 

Bus Wire Length

1.5 mm

2

 (14 AWG)

300 m

0.75 mm

2

 (18 AWG)

150 m

0.50 mm

2

 (20 AWG)

100 m