background image

English

Radio Powr Savr

Installation Instructions 

Please Read Before Installing

Wireless Battery-Powered Occupancy Sensor

LRF5-OCR2B-P  3 V

-

  14 

m

A  865 MHz (Occupancy / Vacancy)

Compatible Products/Additional Information

For a full list of compatible products and other additional information  
visit www.lutron.com/globalenergysolutions

Product Description

Lutron’s ceiling-mounted Occupancy Sensors are wireless, battery-powered, passive infrared (PIR) 
devices that automatically control lights via RF communication with a dimming or switching device. 

Important Notes

1.

   This Sensor is part of a system and cannot be used to control a load without a compatible 

dimming or switching device. Refer to the instruction sheets of the receiving device(s) for 
installation information.

2.

   Use only high-quality lithium batteries, size CR123, 3 V

-

  (ANSI-5018LC, IEC-CR17345). DO 

NOT use rechargeable batteries. Using improperly rated batteries could damage the Sensor. 

   

NOTICE:

 DO NOT disassemble, crush, puncture, or incinerate batteries. DO NOT dispose 

of batteries in normal household waste. Please recycle, take to a proper battery disposal 
facility, or contact your local waste disposal provider regarding local restrictions on the 
disposal or recycling of batteries. 

WARNING: Entrapment hazard.

 To avoid the risk of entrapment, serious injury, or 

death, these controls must not be used to control equipment which is not visible from 
every control location or which could create hazardous situations such as entrapment 
if operated accidentally. Examples of such equipment which must not be operated 

by these controls include (but are not limited to) motorized gates, garage doors, 
industrial doors, microwave ovens, heating pads, etc. It is the installer’s responsibility 
to ensure that the equipment being controlled is visible from every control location 
and that only suitable equipment is connected to these controls. Failure to do so 
could result in serious injury or death.

Sensor Operation

The Sensor will automatically turn the lights on when the space is occupied and automatically 
turn the lights off after the space is vacated.

Instructions

1
2

Before setting up the Sensor, the corresponding dimming or switching device(s) must be installed.

  Twist and remove mounting bracket to insert battery into battery cavity.

A

Pre-Installation

B

Set-Up

C

Sensor Detection Range

D

Sensor Placement and Coverage

 

Before mounting the Sensor, please note the following:

•   

The Sensor is designed for ceiling use only. 

DO NOT

 install on ceilings higher than 12 ft (3.7 m).  

(See section C. 

Sensor Detection Range

)

•   

The Sensor should be installed in a location where it has a good view of all parts of the room. The Sensor 
requires line of sight to operate properly. 

If you cannot see the Sensor, it cannot see you. 

The Sensor 

cannot see through glass objects such as patio or shower doors. (See section C. 

Sensor Detection Range

)

•    DO NOT

 mount the Sensor within 6 ft (1.8 m) of HVAC vents or microwave ovens, within 6 in (15 cm)  

of other RF devices, or within 4 ft (1.2 m) of light bulbs installed below the ceiling line. (See section  
C. 

Sensor Detection Range

)

•   

The Sensor may be installed up to 60 ft (18.3 m) away from the associated dimming or switching device(s) if 
they are in direct line of sight. If there are walls or other barriers between the Sensor and receiving device(s), 
the Sensor should be located within 30 ft (9.1 m). (See section C. 

Sensor Detection Range

)

•  

 Whenever possible, avoid placing the Sensor in a location where it has a broad view outside the intended 
space. If this is unavoidable, the lens can be masked to block the view of undesired areas  
(see www.lutron.com/occsensors).

Lutron Electronics Co., Inc.

7200 Suter Road

Coopersburg, PA 18036-1299, U.S.A.

P/N 041-337 Rev. B    10/2011

•  Easy-to-follow 

Instructions

    P/N 041-337b

13 ft (4.0 m) 

Radius of Coverage at Floor when 

mounted on an 8 ft (2.4 m) Ceiling

  15 ft 

12 ft 

9 ft 

6 ft 

3 ft 

0 ft 

3 ft 

6 ft 

9 ft 

12 ft  15 ft

 (4.6 m)  (3.7 m)  (2.7 m)  (1.8 m)  (0.9 m)  (0 m)  (0.9 m)  (1.8 m)  (2.7 m)  (3.7 m)  (4.6 m)

8 ft

(2.4 m)

Ceiling

height

Ceiling

Floor

Radius of Coverage at Floor

Sensor

Occupant

18 x 18 ft (5.5 x 5.5 m) 

Maximum Room Dimensions 

for Complete Coverage when 

mounted on an 8 ft (2.4 m) Ceiling

Lutron is a registered trademark and Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. ANSI is a registered trademark 

of the American National Standards Institute. IEC is a trademark of the International Electrotechnical Commission.  
© 2011 Lutron Electronics Co., Inc.

Limited Warranty

Lutron EA Ltd. (“Lutron EA”) warrants each unit to be free from defects in material and workmanship and to 
perform under normal use and service. To the extent permitted by law, Lutron EA and Lutron Electronics Co. Inc. 
(“Lutron”) make no warranties or representations as to the units except as set forth herein. This warranty shall 
run for a period of two years from the date of purchase and Lutron’s obligations under this warranty are limited 
to remedying any defect, replacing any defective part or replacement (at Lutron EA’s sole option) and shall be 
effective only if the defective unit is shipped to Lutron EA postage prepaid within 24 months after purchase of 
the unit. Repair or replacement of the unit does not affect the expiry date of the warranty. This warranty does not 
cover damage or deficiencies due to abuse, misuse, inadequate wiring or insulation or use or installation other 
than in accordance with instructions accompanying the unit. To the extent permitted by law, neither Lutron EA 
nor Lutron shall be liable for any other loss or damage including consequential or special loss or damages, loss of 
profits, loss of income, or loss of contracts arising out of or relating to the supply of the unit or the use of the unit 
and the purchaser assumes and will hold harmless Lutron EA and Lutron in respect of all such loss or damage. 
Nothing in this warranty shall have the effect of limiting or excluding Lutron EA’s or Lutron’s liability for fraud or for 
death or personal injury resulting from its own negligence, or any other liability, if and to the extent that the same 
may not be limited or excluded as a matter of law. This warranty does not affect the statutory rights of consumer 
purchasers of this product. Although every attempt is made to ensure that catalogue information is accurate and 
up-to-date, please check with Lutron EA before specifying or purchasing this equipment to confirm availability, 
exact specifications, and suitability for your application. 

Technical Assistance

For questions concerning the installation or operation of this product, call the  

Lutron Technical Support Center.

 Please provide exact model number when calling.

India, New Delhi

+91.124.471.1900

United Kingdom

0800.282.107 or +44.(0)20.7680.4481

Other countries 24/7  

 

+1.610.282.3800
www.lutron.com

In order for the Sensor to operate properly, it must first be set up with a corresponding dimming or 
switching device/system. Consult www.lutron.com/occsensors and click on “Coordinating products” 
to find your system.

18 x 18 ft (5.5 x 5.5 m)

Maximum Room Dimensions

for Complete Coverage when

mounted on an 8 ft (2.4 m) Ceiling

13 ft (4.0 m)

Radius of Coverage at Floor when

mounted on an 8 ft (2.4 m) Ceiling 

15 ft

(4.6 m)

12 ft

(3.7 m)

9 ft

(2.7 m)

6 ft

(1.8 m)

3 ft

(0.9 m)

0 ft

(0 m)

3 ft

(0.9 m)

6 ft

(1.8 m)

9 ft

(2.7 m)

12 ft

(3.7 m)

15 ft

(4.6 m)

Sensor

Occupant

r

Ceiling

Floor

8 ft

(2.4 m)

Ceiling 

height

Radius of Coverage at Floor

Sensor Coverage Chart (for sensor mounted in center of room)

Ceiling height

Maximum room dimensions

for complete floor coverage*

324 ft

2

 (30.2 m

2

)

400 ft

2

 (37.2 m

2

)

484 ft

2

 (44.9 m

2

)

676 ft

2

 (62.4 m

2

)

8 ft (2.4 m)

9 ft (2.7 m)

10 ft (3.0 m)

12 ft (3.7 m)

18 ft x 18 ft (5.5 m × 5.5 m)

20 ft x 20 ft (6.1 m × 6.1 m)

22 ft x 22 ft (6.7 m × 6.7 m)

26 ft x 26 ft (7.9 m × 7.9 m

*  12 ft (3.7 m) is the recommended maximum mounting height