background image

 

A

  Press and release the “Cal.” button on the  

Daylight Sensor.

 

B

  Turn lights in room on using the Relay Toggle  

button on the PowPak Relay Module or an  
associated Pico.

 

C

  Press and hold the “Cal.” button for 6 seconds.

 

D

  Exit room for 5 minutes to allow calibration to be completed.

Note:

 When calibration has completed, all lights will flash and 

begin to respond to daylight.

vive.lutron.com

X

Programming with a Vive Hub

2

 

A

 

Use an iOS

®

 or Android

®

  

compatible device.

 

C   

Open the app and follow the 
instructions.

 

  Note:

 For further information on set up, 

programming, and troubleshooting with a 
Vive system, please refer to the installation 
instructions included with the Vive hub or 
visit www.lutron.com/vive

 

  

Note:

 For programming the PowPak Relay 

Module without a Vive hub see below.

X

Vive

 

Download the Lutron  
Vive app.

PowPak 

|

 Programming without a Vive Hub

 Start Here

1

 

A

 

PowPak Relay Module can be installed in a junction 
box or marshalling box using the conduit nut 
(provided) or with mounting screws (not provided). 
Please consult local and national electric codes for 
proper installation.

If installing unit inside a junction box, please see 
Application Note #423 (P/N 048423) at  
www.lutron.com

 

B

  Once installed, energize the PowPak Relay Module.

 

C

  Use the Relay Toggle button to toggle between high-

end and OFF to verify wiring.

Install PowPak Relay Module

Suggested Installation Location: Center of 
room to ensure proper RF coverage of area.

Part of the Vive Family

PowPak | Installation

Relay Module

English

041647 
Rev. A 
03/2018

RMJS-16R-DV-B | URMJS-16R-DVB |  
RMJS-16R-DV-B-EM  
With Softswitch 

 

RMJS-16RCCO1DV-B | URMJS-16RCCO1DVB   
With Softswitch

 

 and Occupancy-Status CCO 

120 / 277  V

~

  50 / 60 Hz  16 A   

1/2 HP at 120 V

~  

1

1

2

 HP at 277 V

~

Shock Hazard. May result in serious injury or death.  

Turn off power at circuit breaker before installing the unit.

WARNING

All Wireless Transmitters must be installed within  
30 ft (9 m) of the PowPak Relay Module. 

Radio Powr Savr

  

Occupancy  

Sensor

30 ft (9 m) 

Maximum

40 ft (12 m)

30 ft (9 m)

PowPak 

Relay Module

 

Install in center of room to  

maximize RF coverage.

Pico  
Remote 
Control

Note for Replacement:

RMJS and URMJS - the "S" model can replace the non-"S" model

 Important 

Notes: 

Please read before installing.

•  

For installation by a qualified electrician in accordance with all local and national 
electrical codes (including periodic testing and maintenance of emergency 
systems). 

• 

Note:

 Use copper conductors only.

• 

Check to see that the device type and rating is suitable for the application.

• 

DO NOT

 install if product has any visible damage.

• 

 If moisture or condensation is evident, allow the product to dry completely

 before 

installation.

• 

Operate between 32 °F (0 °C) and 131 °F (55 °C).

• 

0% to 90% humidity, non-condensing.

• 

For indoor use only. 

RMJS-5R-DV-B 

RMJS-5RCCO1-DV-B   
With Occupancy-Status CCO 

120 / 277  V

~

  50 / 60 Hz  5 A   

1/6 HP at 120 V

~  

1/3 HP at 277 V

~

PowPak Relay Module

 

UL 2043 Plenum Rated
UL 924 Listed (RMJS-16R-DV-B-EM)

Test

Link

Cal.

For each system ensure you have:

At least one PowPak Relay Module

At least one Wireless Transmitter

Required Components

Radio Powr Savr Occupancy  
Sensor (10 maximum)

PowPak Relay Module

Load  
Status  
LED

Relay Toggle

Advanced 
Operations

Contact 
Closure 
Output 
(CCO)
(Class 2)

(Occupancy-Status CCO Option Shown)

Relay Module 
without 
occupancy-status 
CCO also 
available.

Radio Powr Savr 
Daylight Sensor
(1 maximum)

Pico  
Remote Control  
(10 maximum)

Customer Assistance      www.lutron.com/support

+

Reset Factory Defaults

 

 Note:

 In some instances it may be necessary to reset the 

PowPak

 Relay Module back to factory default settings. 

Triple-tap the Advanced Operations (“ADV”) button on the 
Relay Module and hold until the LED begins to flash slowly.

Within 3 seconds of flashing, release and triple-tap the button 
again and the LED will flash rapidly indicating that the unit has 
been reset to factory defaults.

 Note: 

Any associations or programming previously set up with 

the unit will be lost and will need to be re-programmed.

CCO Information

   Some PowPak Relay Modules include a dry contact closure 

output that provides occupancy status to 3rd-party equipment 
such as building management systems, HVAC, and VAV 
controllers. 

   CCO provides both normally open (NO) and normally closed (NC) 

maintained-type outputs.

   CCO rated to switch resistive loads at 

voltages up to 24 V only. To properly 
control inductive load types such as 
relays, solenoids, or motors, refer to 
Application Note #434.

Switching 
Voltage

0-24 V

-

0-24 V

~

Resistive 
Load

 

1.0 A
0.5 A

R

Note:

 When wiring a CCO model

 

to 

3rd-party systems, use  
20 AWG to 16 AWG (0.5 mm

to  

1.5 mm

2

) solid or stranded wire.

To 3rd Party Equipment

NO

 

(Normally Open)

NC

 

(Normally Closed)

COM

 

(Common)

CCO operation affected only by  
associated occupancy or vacancy sensors.

Room Occupied:

 

NO = Close  NC = Open

Room Unoccupied:

  NO = Open  NC = Close

Line/Hot 
(Black)

Neutral

Switched  
Line/Hot (Red)

To Normal Load

Neutral (White)

1/2 in (21 mm) Knockout Opening

Conduit Nut

To Emergency 
Loads

Emergency  
Backup Generator

Automatic  

Transfer  

Switch

Regular  
Utility Power

Neutral 

120 / 277  V

~

  Normal Feed

Neutral 

120 / 277  V

~

  Emergency Feed

Note:

  For periodic testing and maintanance of 

emergency systems, use the toggle button 
of the RMJS-16R-DV-B-EM to ensure proper 
operation. Make sure PowPak buttons remain 
accessible.

Note:

  Momentary power outages can envoke 

emergency mode on the relay module.  
See 

Troubleshooting

 section for details.

RMJS-16R-DV-B-EM only

Line/Hot 
 (Black)

Neutral

Switched  
Line/Hot (Red)

Neutral (White)

Associate Wireless Transmitters to PowPak Relay Module

Before beginning this step, make sure that there are no other PowPak modules being set up within the same building. It is possible that Wireless 
Transmitters from other systems can be incorrectly associated to this system.

1

 

A

 

Hold the Relay 
Toggle button on 
the PowPak Relay 
Module for 6 seconds  
to enter association 
mode.

 

B

 

Hold the indicated button 
on a Wireless Transmitter 
for 6 seconds to 
associate the device.* 
Repeat for any additional 
Wireless Transmitters.

 

C

 

Hold the Relay Toggle button on 
the PowPak Relay Module for 6 
seconds to save association(s).

*  If no 

g

 button, hold 

“Lights Off” button.

Note:

 The load 

will flash once 
after each step to 
confirm successful 
completion.

Test

Link

Cal.

Calibrate the Radio Powr Savr 
Daylight Sensor 

Daylight Sensor will control all wired fixtures equally.

2

 

D

 

Permanently install wireless 
transmitters (consult individual 
component installation guides for 
information).

Test

Link

Relay 
Toggle

Advanced 
Operations

Lutron, Pico, PowPak, Softswitch, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in 
the U.S. and other countries and is used under license. Google is a registered trademark and Android and Chrome are trademarks of Google Inc.NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.  ©2013 – 2018 Lutron Electronics Co., Inc.

Lutron Electronics Co., Inc. | 7200 Suter Road 
Coopersburg, PA 18036-1299, U.S.A.

Customer Assistance  |  1.844.LUTRON1   

U.S.A., Canada, and the Caribbean

  |  +44.(0)20.7680.4481 

Europe

  |  +1.610.282.3800 

Others

  |  www.lutron.com/support

     

Limited Warranty:

  

www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf

For FCC/IC information:

 Please visit: www.lutron.com/fcc-ic

Load does not respond to 
Wireless Transmitter(s)

•  Ensure breaker to the PowPak Relay Module is on.
•  Ensure the load has been properly wired to the PowPak Relay Module.
•  Ensure Wireless Transmitter is properly associated to PowPak Relay 

Module.

•  Ensure Wireless Transmitter’s battery is installed correctly.

Wireless Transmitter(s) 
cannot be associated to 
PowPak Relay Module

•  The maximum number of Wireless Transmitters have been 

associated to the PowPak Relay Module. To remove a previously 
set up Wireless Transmitter, tap the button used for association on 
the Wireless Transmitter three times, on the third tap hold for three 
seconds and then tap three more times.

PowPak is in emergency 
mode  
(RMJS-16R-DV-B-EM only)

•  In systems with a Vive hub: Contact Lutron Customer 

Assistance for further details.

•  In systems without a Vive hub: Wait 90 minutes for the PowPak 

to return to normal operation.

PowPak will not go into 
emergency mode  
(RMJS-16R-DV-B-EM only)

• Contact Lutron Customer Assistance for further details.

Troubleshooting 

www.lutron.com/support

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be  
followed including the following:

READ AND FOLLOW ALL SAFETY 
INSTRUCTIONS.

•  Do not use outdoors.
•  Do not mount near gas or electric heaters.
•  

Equipment should be mounted in locations and at heights where it will not be 
subjected to tampering by unauthorized personnel.

•  

The use of accessory equipment not recommended by the manufacturer may cause 
an unsafe condition.

•  Do not use this equipment for other than its intended use.

SAVE THESE INSTRUCTIONS

Junction Box

Junction Box

1/2 in (21 mm) 
Knockout Opening

Conduit Nut

Reviews: