Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Test
Link
B
Hold the indicated button on each transmitter for 6 seconds. The fixture will flash to show that wireless
transmitters have been associated. Alternatively, for Radio Powr Savr
T
occupancy/vacancy and daylight
sensors, the green laser pointer can be used. See Application Note #407 on www.lutron.com for more
information.
To associate another transmitter, repeat steps
2A
and
2B
.
A
Initiate association mode on the fixture control by shining a green laser pointer (by others) at the laser
detection hole on the sensor until the load attached to the control module starts flashing (every 2 seconds).
Alternatively, press and hold the
Toggle
button “
” for 6 seconds on the fixture control to initiate
association mode.
Note:
Multiple fixture controls can be placed into association mode by repeating one of the two above methods for the next
fixture control prior to moving to Step 2B.
Associate Transmitters to Fixture Control
Before beginning this step, make sure that there are no other fixture controls being set up in the building which
are currently in association mode. It is possible that wireless transmitters from other systems can be incorrectly
associated to this module.
Important Note:
To optimize RF performance of the product:
– Keep the lamp wiring as short as possible to reduce the radiation from
the lamp wires.
– Keep the lamp wiring as far as possible from the PowPak
R
Wireless
Fixture Control mounting location.
See the Troubleshooting section for more details.
PowPak
R
Fixture Control Knockout
PowPak
R
Fixture Control Wiring
Lamp Wiring
Maximize Distance
Technical Assistance | 1.800.523.9466
USA, Canada, and the Caribbean
| +44.(0)20.7702.0657
Europe
| +1.610.282.3800
Others
| www.lutron.com
Part of the Energi TriPak
®
Family
PowPak
®
Fixture Controls
Installation
Required Components
For each fixture, you will need:
PowPak
R
Fixture Sensor
(FC-SENSOR or
FC-VSENSOR)
(1 maximum)
Pico
R
Wireless
Control
(10 maximum)
6 mA maximum for the control lines. Switches up to 1 A total
(or maximum 3 ballasts or drivers). May be pre-installed in fixture.
PowPak
R
Wireless Fixture Control
(FCJ-010 or FCJ-ECO)
Raise
Toggle
Lower
Load
Status
LED
Consult the fixture installation guide for fixture wiring.
Start Here
English
Important Notes:
• For installation by a qualified electrician in accordance with all local and
national electrical codes.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
120 – 277 V
~
50 / 60 Hz 1 A switching
FCJ-010
0–10 V
-
FCJ-ECO
Lutron
®
EcoSystem
®
PowPak
®
Wireless Fixture Control
UL 2043 Plenum Rated
Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
Provides IEC SELV / NEC
R
Class 2, 12 V
-
, 25 mA to a PowPak
R
fixture sensor
(FC-SENSOR or FC-VSENSOR).
PIR Lens
Laser
Detection
Daylight Lens
Radio Powr Savr
T
Occupancy/Vacancy
Sensor
(10 maximum)
Radio Powr Savr
T
Daylight Sensor
(1 maximum)
Install Fixture Control and Optional Fixture Sensor
Suggested Installation Location: Close to the Fixture / Troffer.
The fixture control can be installed on a fixture/troffer, junction box or marshalling box using the conduit nut
(provided) or with mounting screws (not provided). Please consult local and national electric codes for proper
installation.
A
Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using the adhesive strip
(included). The two communication wires from the sensor attach to the fixture control stab-in connectors. The
wires are interchangeable to eliminate miswiring.
B
Once installed, energize the control module. The fixture will turn on.
WARNING! Shock Hazard.
May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
6 mA sink/source
Notes:
1. Fixture control can be used
without a fixture sensor as long
as at least one Radio Powr
Savr
T
sensor or Pico
R
wireless
control is used.
2. Only one fixture control can be
used per fixture sensor, and
only one fixture sensor can be
used per fixture control.
Pico
®
wireless
control
30 ft (9 m)
maximum
PowPak
R
Fixture
Control
Install the fixture control directly to a fixture or
on a junction box nearest to the fixture. Install
the sensor on the ceiling near the fixture to
optimize coverage in the desired area.
Fixture
Control
Sensor
For more information, see
www.lutron.com/TechnicalDocumentLibrary/369866.pdf
Notes:
1. Control wires (Violet/Gray for FCJ-010 or Violet/Violet for FCJ-ECO) can
be run as either Class 1 or Class 2.
2. If hanging pendant fixtures the maximum wire length between fixture
sensor and fixture control is 12 ft (3.7 m). Sensor should be mounted no
more than 2 ft (0.6 m) from the fixture.
3. To install unit inside a junction box, please see Application Note 423 on
www.lutron.com
4. The fixture control needs to be accessible for some programming steps.
Record where it is mounted so that it can be easily located later.
5. When using a Radio Powr Savr
T
daylight sensor in conjunction with both
a PowPak
R
wireless fixture control and PowPak
R
fixture sensor, the
Radio Powr Savr
T
daylight sensor will provide the daylighting input to the
control module, and the PowPak
R
fixture sensor daylighting input will be
ignored.
6. When using a Radio Powr Savr
T
occupancy sensor in conjunction with
both a PowPak
R
wireless fixture control and PowPak
R
fixture sensor,
occupancy data from both sensors is used; either one detecting
occupancy will turn the lights on, and the lights turn off only when both
sensors have gone vacant (no longer detect occupancy).
7. For more information on the PowPak
R
fixture sensor, see: Document
369866 or 048556 on www.lutron.com
For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
Wireless sensors
and controls must
be located within
60 ft (18 m) line of sight,
or 30 ft (9 m), through walls, of
the associated control module.
041485
Rev. A
04/2015
Please read before installing.
+
One Fixture Control
At least one of these transmitters (22 total allowed)
FCJ-010:
At least one 0 – 10 V Fluorescent Ballast or LED Driver
FCJ-ECO:
At least one Lutron
®
EcoSystem
®
Ballast or LED Driver
+
1
2
120 – 277 V
~
50 / 60 Hz 1A switching
14 V
-
6 mA
OR
Laser Detection
Green laser specifications:
• Wave output: constant
• Wavelength: 532 nm
• Output power: 5 mW
Note:
The fixture control will automatically exit
association mode 10 minutes after the last activity.
Wireless Controls:
All lights
Default Functionality
Fixture Controls
Auto On level:
FC-SENSOR only
(not applicable for FC-VSENSOR)
Varies with ambient light level when occupancy is triggered
(e.g., 100% for a dark room, 10% for a bright room).
Timeout period:
15 minutes
On:
100% ;
Favorite
: 50%;
Off
: 0%
Green/Yellow
Neutral
Switched
Hot/Live
Violet
Gray
Fixture Earth
+
–
To additional 0 – 10 V fixtures
Hot (Black)
Neutral
+
–
NEU
HOT
Class 2
MAINS
+
–
NEU
HOT
Class
2
MAINS
+
Violet (both FCJ-010 and FCJ-ECO)
–
Gray (FCJ-010) / Violet (FCJ-ECO)
Fixture Earth
Green/Yellow
Switched Hot (Red)
Hot (Black)
Neutral (White)
Neutral
Fixture/Troffer
or Junction
Box
1/2 in (21 mm) Knockout Opening
From back
of sensor
Ballast / Driver
Conduit Nut