background image

Assemble

Mount and Install

Associate

Connect

1

3

4

2

a.  

 Insert the Pico

®

 control wiring connector through the 

hole in the unmounted wallplate adapter.

a.  

 Carefully mount and align the wallplate adapter.

b.  

 Attach wallplate adapter to wallbox with provided screws.

c.  

 Snap wallplate onto wallplate adapter.

a.  

 Turn on power to the Wallstation control by energizing the link.

b.  

 Wallstation controls must be programmed through the Lutron

®

 

Hospitality System Guestroom Control unit’s software before the 

controls will function as described.*

*  Door chime functionality requires the installation and programming of the door 

chime components

a.  

 Wire the connector terminals to the QS link wiring in wallbox. See 

QS 

Link Wiring Notes

 for further details.

b.  

 Connect the Pico

®

 control connector to the QS link of the Lutron

®

 

Hospitality Room Controller.

b.

   Slide the Pico

®

 control onto the wallplate adapter guide rails that 

match the opening in the wallplate.

Pico

®

 Wallstations

Installation

For use with Lutron

®

 Hospitality Guestroom Solution

Important Notes

Please read before installing

•  For installation by a qualified electrician in accordance with all local and 

national electrical codes. 

•  Operate between 0 °C (32 °F) and 40 °C (104 °F).
•  Do not connect line-voltage wires to wallstation terminals. Improper 

wiring can result in personal injury or damage to the control or to other 

equipment.

•  Use only a cloth with warm water and mild soap to clean faceplates (no 

chemical cleaners).

QSWP-DM

QSWP-CP

IEC PELV/NEC

®

 Class 2  24 V

-

  

30 mA

Required Components 

For each system, ensure that you have:

One for each single Pico

®

 Control: 

Wallplate/Wallplate Adapter kit 

(PWP-S1, PWP-S2, PWP-D3, PWP-D4)

Pico

®

 Privacy Control (QSWP-DM) 

and

/

or

  

Pico

®

 Corridor Control (QSWP-CP)

Top LED 

(green)

Top Button: 

toggle for 

make-up-room 

request

Bottom LED 

(red)

Bottom Button:  

toggle for  

do-not-disturb 

request

Top LED 

(green)

Button: 

press to 

sound door 

chime

Bottom LED 

(red)

+

 WARNING. Shock Hazard. May result 

in serious injury or death.

 Turn off 

power at circuit breaker before installing 

the unit.

4: MUX

3: MUX

2: 24 V

-

1: Common

Need Help? Call Lutron Technical Support at +44.(0)20.7680.4481 or visit www.lutron.com

QS Link Wiring Notes

•  Operating Voltage: 24 V

-

 (IEC PELV/NEC

®

 Class 2), powered off of the 

QS link or an external 24 V

-

 supply

•  Current Draw: 30 mA maximum
•  Consumes 1 Power Draw Unit (PDU) on the QS link; for more 

information on PDUs, see “Power Draw Units on the QS Link”, Lutron 

P/N 369405 at www.lutron.com

•  Counts as one device and no zones on the QS link
•  For more information regarding Lutron

®

 cable specifications, please see 

Lutron P/N 369597 at www.lutron.com

•  For wire runs over 610 m (2 000 ft), please contact Lutron

®

 Technical 

Support

Terminals

•  Accept up to two 1.0 mm

2

 (18 AWG) wires; 

 

one twisted, shielded pair 0.50 mm

2

 (22 AWG) wire; or 

one 4.0 mm

2

 (12 AWG) wire, typically.

•  For wiring limits, see chart below.

QS Link  

Wiring Length

Wire Gauge

Lutron

®

 Cable 

Part Number

Less than  

153 m (500 ft)

Power (terminals 1 and 2): 

 

1 pair 1.0 mm

2

 (18 AWG)

GRX-CBL-346S 

(non-plenum)
GRX-PCBL-346S 

(plenum)

Data (terminals 3 and 4): 

 

1 twisted, shielded pair 0.50 mm

2

 

(22 AWG)

Up to 610 m 

 

(2 000 ft)

Power (terminals 1 and 2): 

 

1 pair 4.0 mm

2

 (12 AWG)

GRX-CBL-46L 

(non-plenum)
GRX-PCBL-46L 

(plenum)

Data (terminals 3 and 4): 

 

1 twisted, shielded pair 0.50 mm

2

 

(22 AWG)

Troubleshooting

Symptoms

Possible Causes

No communication 

with the Room 

Controller

Miswire or loose connection at the control 

link data lines 3 and 4.

Wallstation LEDs scroll 

in reverse order
Wallstation buttons do 

not work. LEDs and 

buttons do not function 

as intended

Wallstation is miswired. 
Wallstation is not powered. 
Wallstation has been programmed incorrectly. 

LEDs do not light

Miswire or loose connection at wallstation(s) 

or processor on the control link common and 

power connections 1 and 2.

Wallstation has been programmed incorrectly. 

Warranty

For warranty information, please visit 

 

www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf

Technical Assistance

U.S.A. / Canada: 1.800.523.9466
Mexico: +1.888.235.2910
Brazil: +55 11 3257 6745
United Kingdom: +44.(0)20.7680.4481
India: +91.124.471.1900
United Arab Emirates: +971.4.299.1224
China: 10.800.120.1536
Singapore: 800.120.4491
Other Countries: +1.610.282.3800

Pico

®

 Privacy Control

Inside Guestroom

Pico

®

 Corridor Control

Outside Guestroom

IEC PELV/NEC

®

 Class 2 control wiring:

2: 24 V

-

1: Common

4

3

2

1

Drain

Data Link: 1 twisted, shielded pair

4: MUX

3: MUX

Lutron

®

 Hospitality Guestroom Controller 

(GCU-HOSP)

Radio Frequency (RF) Receiver with Door Chime or third-party door bell solution with QSE-IO.

+

+

Lutron, Pico, and 

)

 are registered trademarks of Lutron Electronics Co., Inc.

NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts

©2013 Lutron Electronics Co., Inc.

Lutron Electronics Co., Inc.

 

7200 Suter Road 

|

 Coopersburg, PA 18036-1299

 

TEL: +1.610.282.3800

Start Here

040397 Rev. A

04/2013

English

Summary of Contents for Pico Privacy Control QSWP-DM

Page 1: ...Draw Unit PDU on the QS link for more information on PDUs see Power Draw Units on the QS Link Lutron P N 369405 at www lutron com Counts as one device and no zones on the QS link For more information regarding Lutron cable specifications please see Lutron P N 369597 at www lutron com For wire runs over 610 m 2 000 ft please contact Lutron Technical Support Terminals Accept up to two 1 0 mm2 18 AWG...

Page 2: ...n el QS Link Lutron P N 369405 en Cuenta como un dispositivo y cero zonas en el enlace QS Para obtener más información con respecto a las especificaciones de cables Lutron consulte Lutron P N 369597 en www lutron com En el caso de corridas de cable de más de 610 m comuníquese con el departamento de asistencia técnica de Lutron Terminales Aceptan hasta dos cables de 1 0 mm2 18 AWG un par trenzado y...

Page 3: ...erne de 24 V Consommation de courant 30 mA maximum Consomme 1 unité de consommation électrique PDU sur le QS link pour plus d informations sur les PDU consultez Unités de consommation électrique du QS link pièce nº 369405 de Lutron sur www lutron com Compte comme un appareil et aucune zone sur le QS link Pour plus d informations sur les caractéristiques des câbles Lutron veuillez voir la pièce nº ...

Page 4: ...en zur Leistungsaufnahme über das QS Link in PDU unter www lutron com qs Zählt als 1 Gerät keine Zonen auf dem QS Link Weitere Informationen zu Lutron Kabelspezifikationen finden Sie im Lutron Dokument mit der Best Nr 369597 unter www lutron com Informationen zu Kabellängen ab 610 m erhalten Sie beim technischen Support Zentrum von Lutron Anschlüsse Nehmen bis zu zwei 1 0 mm2 18 AWG Kabel auf In d...

Page 5: ...30 mA max Consuma 1 unità di assorbimento PDU sul link QS per ulteriori informazioni sulle PDU si prega di consultare il documento Lutron N 369405 Unità di Assorbimento sul Link QS disponibile sul sito web www lutron com Conta come un dispositivo e zero zone sul link QS Per ulteriori informazioni sulle specifiche dei cavi Lutron si prega di consultare il documento Lutron N 369597 disponibile sul s...

Page 6: ...ermogensverbruik eenheid Power Draw Unit PDU op de QS link voor meer informatie omtrent PDU s raadpleeg Vermogensverbruik eenheden op de QS link Lutron P N 369405 op www lutron com Telt als één apparaat en nul zones op de QS link Voor meer informatie omtrent Lutron kabelspecificaties raadpleeg Lutron P N 369597 op www lutron com Neem voor draadverbindingen van meer dan 610 m contact op met de Lutr...

Page 7: ...максимум 30 А Потребляет 1 единицу передаваемой мощности PDU на канале QS для получения дополнительной информации о PDU см Power Draw Units on the QS Link Lutron P N 369405 по адресу www lutron com Считается одним устройством нет зон на канале QS Для получения дополнительной информации о технических характеристиках кабелей Lutron см Lutron P N 369597 по адресу www lutron com С вопросами о прокладк...

Page 8: ...任何区域 欲了解有关 Lutron 电缆规格的更多信息 请参阅www lutron com中 Lutron 部件号369597 对于超过610 m 的线路 请联系Lutron 技术支持部 端子 接受最多两根1 0 mm2 18 AWG 的导线 一根0 50 mm2 22 AWG 的屏蔽双绞线 或一根 4 0 mm2 12 AWG 的导线 通常情况下 布线限制请参阅以下图表 QS 链路 布线长度 线规 Lutron 电缆部件号 少于 153 m 功率 端子 1和 2 一对 1 0 mm2 18 AWG GRX CBL 346S 非阻燃 GRX PCBL 346S 阻燃 数据 端子 3 和 4 1根 0 50 mm2 22 AWG 的屏蔽 双绞线 最长 610 m 功率 端子 1和 2 一对 4 0 mm2 12 AWG GRX CBL 46L 非阻燃 GRX PCBL 46L 阻燃 数据 端...

Reviews: