Appendix B: Installation Worksheet
It is recommended that before beginning to configure the SMC55-HWQS, the required values for the necessary parameters should be
marked. The values required to configure the HVAC system can be written in this worksheet and used by the installer during configuration.
Job Name:
HVAC system type:
Table 20: Basic Configuration Parameters
Applicable
Systems
Basic
Configuration
Parameter
Name
Description
Default Value
Range
Value to
be Set
All
01b
System Type
00: Conventional system
01: Heat pump
02: 2-Pipe FCU
03: 4-Pipe FCU
04: Underfloor radiant heat
05: Underfloor electric heat
00:
Conventional
system
00–05
Heat
Pump
1
and
Conventional
02b
Heat Stages
00: None (No Heat Stage)
01: 1 Stage (W
1
)
02: 2 Stage: 1 Compressor and 1 Auxiliary
03: 2 Stage: 2 Compressor, No Auxiliary
04: 3 Stage: 2 Compressor and 1 Auxiliary
01: 1 Stage
(W
1
)
00–04
03b
Run Auxiliary Heat
(Aux/W
2
) with
other heat stages
00: No
01: Yes
Skipped if no Aux/W
2
01: Yes
00–01
04b
Auxiliary Heat
(Aux/W
2
) upstage
delay
00: 0 minutes
01: 1 minute
02: 2 minutes
03: 5 minutes
04: 10 minutes
05: 20 minutes
06: 30 minutes
07: 1 hour
08: 2 hours
09: 4 hours
10: 8 hours
11-24: 11-24 hours
Skipped if no Aux/W
2
05: 20
minutes
00–24
05b
Cool Stages
00: None (no cool stage)
01: 1 Cool stage (Y1)
02: 2 Cool stages (Y1, Y2)
01: 1 Cool
stage (Y1)
00–02
Heat Pump
1
06b
Heat Fan Control
00: Equipment controls fan
01: Thermostat controls fan
01:
Thermostat
controls fan
00–01
07b
Changeover /
Reversing Valve
(O/B)
00: On for cooling (O)
01: On for heating (B)
00: On for
cooling (O)
Fan Coil Units
and Radiant
Floor
1
08b
Valve / Element
Type
00: Relay
01: 0–10 V
-
02: Floating point (Fan coil units only)
00: Relay
00–01
Fan Coil Units
09b
Fan Type
00: Relay (G1, G2, G3)
01: 0–10 V
-
00: Relay (G1,
G2, G3)
00–01
10b
2-pipe Mode
01: Heat only
02: Cool only
03: Changeover
03:
Changeover
01–03
Radiant Floor
2
11b
Floor Control Type
01: Indoor air only
02: Indoor air and floor limiting
03: Floor temperature only
01: Indoor air
only
01–03
1
Included with SMC55-RESI version 7302 or newer and HomeWorks Palladiom Thermostat version 1.10 or newer.
1
Included with SMC55-HWQS version 7420 or newer, SMC55-RESI version 7302 or newer and HomeWorks Palladiom Thermostat version 1.10 or newer.