Limelight by Lutron
Gateway Panel Installation
English
Important Notes:
• Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
• Operate between -4 °F – 122 °F (-20 °C – 50 °C), ambient.
• For more information, see
www.lutron.com/TechnicalDocumentLibrary/3691100.pdf
• Install in accordance with all local and national electrical codes.
• Equipment is intended for installation in a restricted access area.
• Protective earthing is provided by the socket outlet, which powers the
gateway. All wiring must be verified by a licensed electrician.
• Socket outlet shall be easily accessible after installation.
• Install within 5 ft (1.5 m) of a power outlet/receptacle (power cord length
is 5 ft [1.5 m]).
• Product weight is approximately 7.5 lbs (3.4 kg).
• Gateway: For Emergency applications – The gateway MUST be installed
on normal power only (NOT Emergency) for proper system functionality.
• Fixtures: For Emergency applications – Devices require a 1 second delay
before emergency power is applied after loss of normal power for proper
system functionality. To ensure proper system functionality, this device
CANNOT be installed on an Uninterruptable Power Supply (UPS)
backup system.
Standards:
• cULus Listed
• FCC15.247 / IC RSS-247
LL-ETHGATE
LL-CELLGATE
Please read before installing
120 V
~
60 Hz 0.6 A maximum
current draw, 15 W (51.2 BTU/hr)
max power consumption
041663
Rev. E
05/2020
FCC / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-
exempt RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) This device must accept any interference, including interference that may cause
undesired operation. Modifications not expressly approved by Lutron Electronics Co.,
Inc. could void the user’s authority to operate this equipment.
Note:
This equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
• Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected
• Consult the dealer or an experienced radio/TV technician for help
)
Lutron, Lutron, and Limelight are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries.
©2018–2020 Lutron Electronics Co., Inc.
Installation
1. Install provided antenna(s). For LL-CELLGATE: install antennas in designated ports indicated by product label.
2. Follow Mounting Notes and Wireless Range table below to mount the gateway. Keep in mind it may need to
be relocated to improve performance.
3. For LL-ETHGATE: Configure IT Network per IT guide (www.lutron.com/limelightITguide) and wire Ethernet
cable to the gateway.
4. Power the gateway and monitor the display for any connection issues. Refer to Troubleshooting section if
errors occur.
Mounting Notes
• Four (4) mounting brackets pre-attached
• Wall anchors (supplied by others)
• Mount vertical with space for field service access to side connectors
• Do not install in direct exposure to the sun or the elements (suggested installation location is in a
maintenance closet)
• Mount away from dense metal obstructions (maintain at least 2 ft [0.6 m])
• Mount in a location that minimizes the distance from the farthest controlled fixture
Connections
• Ethernet (LL-ETHGATE only)
– CAT5 (or equivalent) cable, straight-through wiring (T568B) cable supplied by others
– Field wired with RJ45 Ethernet plug (by others)
– Waterproof mating connector
· Requires field crimped connector (RJ45 crimp tool supplied by others)
– IT Network Configuration: www.lutron.com/limelightITguide
• Cellular (LL-CELLGATE only)
– Verizon 4G LTE technology
– Ethernet connection is disabled from being used as the system connection. Intended for Lutron Field
Service Representatives only
Wireless Range Best Practices
RF range recommendations
Parking Garage
Flat lot
3 nodes within this distance of the gateway
50 ft (15.2 m)
150 ft* (45.7 m)
Max distance from the gateway to any one node
500 ft (152.4 m)
3000 ft (914.4 m)
Max distance from node to node
50 ft (15.2 m)
150 ft (45.7 m)
Gateway proximity to dense metal obstructions
(including electrical panels)
Minimum 2 ft (0.6 m) away at height of no
less than 6 ft (1.8 m)
Minimum 2 ft (0.6 m) away at
height of no less than
6 ft (1.8 m)
Max number of luminaires controlled by a single
gateway
Up to 800, as long as no other range
restrictions are violated. Nodes should be
no farther than 4 floors above or below the
gateway.
Up to 800, as long as no
other range restrictions are
violated
Cloud Connection
Status Rev 2.3
DISPLAY
Limelight
Cellular Antenna
Node Antenna
Mounting
Brackets (4)
PWR
LED
LL-ETHGATE
Limelight by Lutron Gateway with Ethernet
connection, IP65 capable when Ethernet is
installed in the provided grommet,
120 V
~
60 Hz with 5 ft (1.5 m) power cord
LL-CELLGATE
Limelight by Lutron Gateway with cellular
connection, IP65 capable when Ethernet is
installed in the provided grommet,
120 V
~
60 Hz with 5 ft (1.5 m) power cord
To network (QS-EO or
Corporate ethernet network)
(LL-ETHGATE only)
To network (QS-EO
or Corporate ethernet
network)
To Limelight by Lutron
cloud
To Limelight by Lutron
system nodes
To Limelight by Lutron
system nodes
Typical One-Line Diagram Components
Troubleshooting
Shortly after power is applied, the gateway will initiate a self-check sequence. The full self-check sequence runs
~4 minutes and repeats twice. Errors encountered will appear on the screen.
Symptoms
Possible Solutions
LCD is OFF
– LCD light turns off after self-check is complete. This does not signify an issue on its own
– If the Power LED next to the power cord is also off, verify power is connected to the
gateway
LCD Error: Ethernet
Unavailable
– Verify that the wired Ethernet is connected properly
– Verify the IT Implementation Guide was followed for the Ethernet port that was wired to
the gateway: www.lutron.com/limelightITguide
LCD Error: XXX Port XXX
FAIL
– Verify the IT Implementation Guide was followed for the Ethernet port that was wired to
the gateway: www.lutron.com/limelightITguide
No Cell Signal
– Verify antennas were installed correctly per gateway labels and product images in this
document
– Verify there is no dense metal obstructions within 2 ft (0.6 m) of the antennas
– Relocate the Cellular Gateway (LL-CELLGATE) to an area with stronger 4G LTE Verizon
coverage
Other Errors
Contact Lutron Customer Assistance at 1.844.LUTRON1
* If the gateway is not at or above ground level or there is more than one wall between the gateway and nodes, the 50 ft (15.2 m)
spacing guideline should be used.