Installation Instructions
Please Leave for Occupant 

This product is covered by one or more of the following U.S. patents: 4,797,599;
4,803,380; 4,893,062; DES 287,242; DES 311,171; DES 311,382; and corresponding
foreign patents. U.S. and foreign patents pending. Lutron and GRAFIK Eye are registered
trademarks. 

© 1994 Lutron Electronics Co., Inc.

(Unit shown with faceplate removed)

Description

The NGRX-PB increases the GRX-3000 Main Control
single zone load capacity (Incandescent, Magnetic
Low Voltage, and Neon/Cold Cathode only) to
2000W/VA.  
It mounts in a standard 2-gang wallbox (minimum
depth: 2 3/4”, recommended depth: 3 1/2”).
Note: The load of low voltage inductive transformers in VA=
the low-voltage lamp watts x 1.3 (representing a 30%
loss due to the transformers). Example: 5 low-voltage
lamps at 50W each= 250 lamp watts x 1.3 = 325VA.

Installation & Operation

New Installations:
Check each zone for short or open circuits. Turn
power off. Connect a standard switch between the hot
lead and that zone’s load wire, then turn power on.  If
the load device does not operate, the circuit is open.
If the breaker trips (fuse blows), the circuit is shorted.
Correct any open or shorted condition and test again
before proceeding.

1.

Turn power off to GRX 3000 Series Main Control 

Unit and the feed to the NGRX-PB Power Booster.

Warning:

Always turn off the circuit breaker or remove the
main fuse from the power line  before doing any
work. Failure to do so can result in serious
personal injury.

2.

Strip insulation from wallbox wires as shown:

3.

Connect wiring as shown in Figure 1. Each 

terminal will accept up to two wires (#12 to #18 
AWG). Use 75 C° copper (CU) wire only. 
Terminal tightening torque= 9in/lb.

3000 

Series

DO NOT WIRE HOT

UP

UP

NGRX-PB,  2000W/V

A

 120V

AC,  1600W/V

A

 100V

AC

LUTRON

LISTED 243C IND. CONTROL

 EQUIP

.

COOPERSBURG, P

A

  USA

U

L

+

+

D HOT OUT

HOT IN

CONTROL

NEUTRAL

NGRX-PB

GRX-3002        GRX-3004
GRX-3003        GRX-3006

LUTRON

20A BREAKER

FROM

DISTRIBUTION

PANEL

EUTRAL FROM 

TRIBUTION PANEL

LOAD

Any Zone

Figure 1. Wiring Diagram

Important Notes:

1. This control must be installed by a qualified 

electrician.

2. Install in accordance with all applicable regulations.
3. Improper wiring can result in personal injury,

damage to the control, or damage to other 
equipment. 

4. Use only with core-and-coil (magnetic) type low

voltage transformers. Before attempting to 
control a solid-state low voltage transformer,
call Lutron’s toll-free hotline and ask for 
Application Note No. 19, Guide to Dimming 
Low-Voltage Lighting (part number 362-219). 

5. In dimmed low-voltage circuits, to avoid 

excessively high current flow that can cause 
transformer overheating and failure:
(a) Do not operate the unit with all of the lamps

removed or with any inoperative lamps.

(b) Replace any burned out lamps immediately.
(c) Use only transformers which incorporate 

thermal protection or fused primary windings.

To 20A
breaker in
Distribution
Panel

To Neutral in
Distribution
Panel

Dimmed Hot from any zone

NGRX-PB 
POWER BOOSTER

For Incandescent, Magnetic Low Voltage,