Step 1: Wire connections
1.1
Connect one end of the supplied Ethernet cable to an
EcoSystem
®
Energi Savr Node
unit (QSN-1ECO-S,
QSN-2ECO-S) or to an
Energi Savr Node
Ethernet
Programming Interface (QSE-CI-AP-D).
Note:
If more than one QS link is present, these steps
will need to be repeated for each QS link.
1.2
Connect the other end of the supplied Ethernet cable to
one of the standard LAN ports on the wireless router. Do
not plug the cable into the WAN (Internet) port.
1.3
Connect the supplied router power supply to the router
and plug the power supply into a wall outlet. Verify that the
wireless router is powered on by confirming that the lights
on the front of the unit are on.
overview
The
Energi Savr Node
Wireless Setup Kit (C-ESN-SETUP) contains the following items:
•
Apple iPod touch
device preloaded with Lutron
®
Energi Savr Node
setup application (also available
on the
Apple App Store
)
• Wall charger for
iPod touch
• 802.11g wireless router preconfigured to communicate with both
iPod touch
device and
Lutron
Energi Savr Node
units
• Ethernet cable for connecting wireless router to
Energi Savr Node
system
System example
energi Savr Node
™
Wireless Setup Kit
Quick-Start Guide
Note:
The wireless router has already been configured
to communicate with the
Apple iPod touch
device. If
you restore the router to its factory default, you will
need to re-establish wireless communications between
the
Apple iPod touch
device and the router using the
Apple iPod touch
device’s WiFi connection screen.
Step 2: Discover the system
2.1
Remove the
Apple iPod touch
device from the packaging
and power on the device by holding the button on the top
of the unit for several seconds (until the screen becomes
active). Allow some time for the device to boot up.
Note:
You may find that the
Apple iPod touch
device
is not fully charged. If necessary, connect the supplied
Apple iPod touch
device wall charger
to a power source and then plug the
Apple iPod touch
device into the
wall charger.
Wire type and corresponding maximum wire distance:
Type 1
Lutron
GRX-CBL-346S cable: 500 ft (152 m)
Lutron
GRX-CBL-46L cable:
2000 ft (610 m)
Type 2
Standard CAT5/CAT5E cable: 300 ft (91 m).
100 ft (30 m) cable included with kit.
NOTE:
Total wire length not to exceed maximum wire distance shown above.
Wire Type 1
Apple iPod
touch
Wire Type 1
QS Link
QSM
Energi Savr Node
Unit
Wire Type 2
EcoSystem
®
Energi Savr Node
(QSN-2ECO-S,
QSN-1ECO-S) or
ESN Programming
Interface
(QSE-CI-AP-D)
Wireless
Router
To Power