BUTTON AND LED LOCATIONS
TROUBLESHOOTING
WIRED INPUTS
USING THIS GUIDE
OTHER QS LINK DEVICES
QS SENSOR MODULE (QSM) WITH WIRED OR WIRELESS INPUT DEVICES
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Help
1.800.523.9466
U.S.A., Canada and the Caribbean
+1.888.235.2910
México
+1.610.282.3800
Others
This guide is divided into sections. Each section deals with a particular feature or set of features
of the Energi Savr Node
TM
unit and the equipment connected to it. Depending on the connected
equipment and the intended use of your Energi Savr Node
TM
unit, some sections may not apply.
See below to determine which sections should be read.
0-10 V Outputs l Salidas l Sorties
4 X 50 mA
(Sinking Only l Recepcion solamente l Récepteur de courant seulement)
QSN-4T16-S-347
120-277 V
~
50/60 Hz 500 mA
0-10 V / Softswitch
®
24/7 Help | Ayuda | Aide
www.lutron.com
U.S.A. Canadá Caribbean | E.U.A. Caribe | É.-U., Caraïbes 1.800.523.9466
México +1.888.235.2910
Others | Otros | Autres
+1.610.282.3800
Coopersburg, PA 18036, U.S.A.
500-14444 Rev. A
saving energy
since 1961
Energi Savr Node
TM
Type 1
Enclosure
243C
LISTED
Ind.
Cont. Eq.
4 Softswitch® Circuits l Circuitos
Capacity l Capacidad l Capacité :
IEC PELV / NEC® Class 2
Input Groups | Grupos de entrada
Groupes d’entreés : 20 V
-
4 X 65 mA
QS Link | Elance | Liaison : 24 V
-
462 mA
WARNING
Risk of Electric Shock. May Result in serious injury or death.
More than one disconnect may be required to de-energize
this device. Disconnect all power sources before servicing
unit.
ADVERTENCIA
Riesgo choque eléctrico. Puede resultar en lesiones graves o
muerte. Puede necesitarse más de una desconexión para
desenergizar este dispositivo. Desconecte todas las fuentes
de alimentación antes de prestar servicio a la unidad.
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne
ou de graves lésions. Plus d’un débranchement peut être
Débrancher toutes les sources d’énergie avant de procéder
à l’entretien de cette unité.
®
4 x 16 A
120-277 V
~
4 x 0,5 HP
120 V
~
4 x 1,5 HP
277 V
~
4 x 16 A
347 V
~
All Energi Savr Node
TM
units
Read:
»
Load Setup
Energi Savr Node
TM
with Softswitch
®
unit
(QSN-4S16-S, QSN-4S16-S-347, QSN-4S20-S)
Energi Savr Node
TM
for 0-10 V unit
(QSN-4T16-S, QSN-4T16-S-347, QSN-4T20-S)
Type 1
Enclosure
4 Softswitch® Circuits l Circuitos
Capacity l Capacidad l Capacité :
QSN-4S16-S-347
120-277 V
50/60 Hz 500 mA
Softswitch
®
Coopersburg, PA 18036, U.S.A.
500-14445 Rev. A
saving energy
since 1961
Energi Savr Node
TM
WARNING
Risk of Electric Shock. May Result in serious injury or death.
More than one disconnect may be required to de-energize
this device. Disconnect all power sources before servicing
unit.
ADVERTENCIA
Riesgo choque eléctrico. Puede resultar en lesiones graves o
muerte. Puede necesitarse más de una desconexión para
desenergizar este dispositivo. Desconecte todas las fuentes
de alimentación antes de prestar servicio a la unidad.
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne
ou de graves lésions. Plus d’un débranchement peut être
Débrancher toutes les sources d’énergie avant de procéder
à l’entretien de cette unité.
®
24/7 Help | Ayuda | Aide
www.lutron.com
U.S.A. Canadá Caribbean | E.U.A. Caribe | É.-U., Caraïbes 1.800.523.9466
México +1.888.235.2910
Others | Otros | Autres
+1.610.282.3800
243C
LISTED
Ind.
Cont. Eq.
IEC PELV / NEC® Class 2
Input Groups | Grupos de entrada
Groupes d’entreés : 20 V
-
4 X 65 mA
QS Link | Elance | Liaison : 24 V
-
462 mA
4 x 16 A
120-277 V
~
4 x 0,5 HP
120 V
~
4 x 1,5 HP
277 V
~
4 x 16 A
347 V
~
LED Feedback
LED
LED Behavior
Description
Occ
(Occupancy Sensor)
Continuous On
Sensor detects Vacancy
1 flash per second
Sensor detects Occupancy
Off
Sensor never detected
Daylight
(Daylight Sensor )
Continuous On
Sensor is detected
Flashing
Sensor information transmitting on
the QS link
Off
Sensor never detected/sensor not
seeing light
IR
(Infrared Receiver)
Continuous On
Receiver is detected
Flashing
IR button press detected
Off
Receiver never detected
Switch
(NEC
®
Class 2 Switch)
Continuous On
Switch detected/open
Flashing
Switch button press detected
Off
Switch never detected
CCI
(Contact Closure Input)
Continuous On
Contact detected/open
Flashing
Contact closed
Off
Contact never detected
Emerg
(Emergency Contact
Closure Input)
Continuous On
Normal operation/Contact Closed/
Jumpered
Rapid flash
Emergency Mode/Contact Open/
Jumper missing
QS Link
On/Flashing
/
Device transmitting/receiving on the
QS link
3 quick flashes every
4 seconds
Communication error
Off
Device not transmitting/receiving on
the QS link
Wired
Continuous On
Wired sensor
Zone
Continuous On
Load is on
Off
Load is off
Troubleshooting using Symptoms
Symptom
Cause
Solution
Unable to add daylight
sensor to a zone
Existing daylight sensor
already assigned to the zone
Unassign the existing daylight sensor and
try again.
Unable to add an
occupancy sensor to
a zone
16 sensors have already
been assigned
No more than 16 sensors can be assigned
to one ESN unit. Unassign sensors until
below 16 sensor limit.
Daylight sensor fails to
turn on a zone
Occupancy sensor is
overriding the zone
Daylight sensors will not turn a zone on if
an occupancy sensor assigned to that zone
detects that the room is vacant.
Switched zone daylighting:
incorrect light level set during
Daylighting Setup
Reset the daylighting set point. See
Daylighting Setup
.
When associating a
QSM to the Energi Savr
Node
TM
unit, the ‘QSM’
LED flutters for 1
second, then turns off
A QSM has already been
associated to the Energi
Savr Node
TM
unit.
To clear the QSM association and any
Energi Savr Node
TM
unit zone assignments
to any QSM inputs, press and hold the
Input
button on the Energi Savr Node
TM
unit
for 10 seconds. The ‘Input’ LED will flutter
for 1 second, then turn off.
When associating a
wireless input device
to a QSM, the QSM
responds with 10 short
beeps
Maximum number of
associations to the QSM has
been exceeded for that
wireless input device type.
Unassign any unnecessary wireless inputs of
that device type and try again.
When associating a
wireless input device
to a QSM, the QSM
responds with 5 short
beeps
Input device is already
associated to another QSM
on the QS link.
If you choose to ignore the warning and try
to associate the same input device to the
QSM a second time, the input device will be
removed from association with the previous
QSM and will now be associated with the
new QSM. Note: This will also remove any
Energi Savr Node
TM
programming that the wireless device may
have had through the previous QSM.
QS Link LED quickly
flashes 3 times every 4
seconds
QS Link communication
error.
Check QS Link wiring
Technical Assistance
U.S.A. / Canada: 1.800.523.9466 Mexico: +1.888.235.2910 Other Countries: +1.610.282.3800
IMPORTANT NOTES
Energi Savr Node
TM
with Softswitch
®
unit
(QSN-4S16-S, QSN-4S16-S-347, QSN-4S20-S)
Energi Savr Node
TM
for 0-10 V unit
(QSN-4T16-S, QSN-4T16-S-347, QSN-4T20-S)
Energi Savr Node
T
manual programming guide
English
1.
Manual Programming:
This document describes manual
programming via the buttons on the front of the Energi Savr
Node
TM
unit. For programming using the
Apple iPod touch
or
iPhone
mobile digital devices, please see the Energi Savr
Node
TM
app available from the
Apple AppStore
online store.
2. Use only compatible Lutron
®
sensors and controls.
032449 | Rev. C | 05/2014
24/7 Help
U.S.A., Canada and the Caribbean
1.800.523.9466
México
+1.888.235.2910
Others
+1.610.282.3800
Fax
+1.610.282.6311
www.lutron.c
om
If you have wired sensor inputs wired directly to the Energi Savr Node
TM
unit input group terminal
blocks, see below to determine which additional sections to read.
www.lutron.com
© 2014 Lutron Electronics Co., Inc.
P/N 032449 Rev. C 05/2014
Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries.
AppStore is a service mark of Apple Inc.
Lutron, GRAFIK Eye, Pico, seeTouch, Softswitch and
)
are registered trademarks, and Energi Savr
Node and Radio Powr Savr are trademarks of Lutron Electronics Co., Inc.
All Wired Inputs
Read:
»
Energi Savr Node
TM
(ESN)
Unit Wired Input
Setup
OR
Energi
Savr
Node
TM
Unit
LUTRON
Dry Contact
Closure
Switch
Wires to “Switch”,
“CCI”, or “EMERG”
Input
»
Energi Savr
Node
TM
(ESN)
Unit Wired
Input Setup
Wired
Occupancy
Sensor
Wires to “Occ” Input
Additional Sections:
»
Energi Savr Node
TM
(ESN)
Unit Wired Input Setup
»
Occupancy Setup
Wired Wallstation
or Infrared (IR)
Sensor
Wires to “IR” Input
»
Energi Savr
Node
TM
(ESN)
Unit Wired
Input Setup
Wired
Daylight
Sensor
Wires to “Daylight” Input
Additional Sections:
»
Energi Savr Node
TM
(ESN)
Unit Wired Input Setup
»
Daylighting Setup
If you have a QSM wired to the Energi Savr Node
TM
unit QS Link terminal block, read sections
QS Sensor
Module (QSM)
Input Setup and
QS Sensor Module (QSM)
Zone Assignment.
Some parts of the section
may not apply, depending on the devices connected to the QSM. See below to determine which additional sub-
sections to read for each type of connected device.
QSM Wireless Input Devices
Communicates with QSM via Radio Frequency (RF)
Read:
»
Subsection: Associating Wireless Input
Devices to a QSM
QS Sensor Module (QSM)
Wires to “QS Link” Terminal Block on
Energi Savr Node
TM
unit
Wireless
Occupancy
Sensor
Additional Sections:
»
Occupancy Setup
»
Subsection: Assign Zones to
QSM Inputs
Wireless
Daylight
Sensor
Additional Sections:
»
Daylighting Setup
»
Subsection: Assign Zones to
QSM Inputs
Wired
Occupancy
Sensor
Additional Sections:
»
Occupancy Setup
»
Subsection: Assign Zones to
QSM Inputs
Wired
Daylight
Sensor
Additional Sections:
»
Daylighting Setup
»
Subsection: Assign Zones to
QSM Inputs
LUTRON
Pico
®
Wireless
Controller
Additional Sections:
»
Subsection: Assign Zones to Pico
®
Wireless Controller (through QSM)
QS Link
Wired Wallstation
or Infrared (IR)
Sensor
Additional Sections:
»
Subsection: Assign Zones
to QSM Inputs
OR
Energi
Savr
Node
TM
Unit
QS
Sensor
Module
Read:
»
QS Sensor Module (QSM)
Input Setup
»
QS Sensor Module (QSM)
Zone Assignment
QSM Wired Input Devices
Wires to Input Terminal Blocks on QSM
Read:
»
Subsection: Associating Wired
Input Devices to a QSM
QS Link
If you have other devices wired to the Energi Savr Node
TM
unit QS Link terminal block, see below to determine
which additional sections to read.
Energi
Savr
Node
TM
Unit
Wired
seeTouch
®
QS
Wallstation
Additional Sections:
»
Wired seeTouch
®
QS Wallstations Programming
QSE-IO
Input/Output
Interface
Additional Sections:
»
QSE-IO Input/Output Interface Programming
CCI
1
CCI 2
CCI 3
CCI 4
COM
CCI 5
V
0-24 V
1 A
0-24 V
½ A
R
O
N
CCO 1 NC
CCO 1 NO
CCO 2 NC
CCO 2 NO
1-2 COM
CCO 3 NC
CCO 4 NO
CCO 3 NO
CCO 4 NC
3-4 COM
CCO 5 NC
5 COM
CCO 5 NO
V
R
MUX
COM
V+
MUX
500-13491 Rev
. B
CCO 1
CCO 2
CCO 3
CCO 4
CCO 5
ST
A
T
QS
800.523.9466
+
1.610.282.3800
www.lutron.com/qs
QSE-IO
24 V 100 mA
®
243C IND. CONT. EQ.
0
2 7 5 5 7 6 1 3 2 3
1
8 7 6 5 4 3 2 1
4 3 2 1
GRAFIK Eye
®
QS
Control Unit or
QS Timeclock
Additional Sections:
»
GRAFIK Eye
®
QS Control Unit or QS Timeclock Programming
LUTRON
Zones
Inputs