background image

Energi Savr Node

TM

 QS | Programming Guide

Energi Savr Node

TM

 QS 

|

 Programming Guide

Lutron

®

  

|

  6

QS Link Input(s) Setup

To assign a seeTouch

®

 QS Wallstation or GRAFIK Eye

®

 QS unit to any 

Energi Savr Node

 QS unit zone on the 

QS link, follow the steps below.

seeTouch

 QS Wallstation - Scenes and Off

1. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds. The QS link 

enters Programming Mode. The sensor Group A and Group B LEDs and the ‘H’, ‘M’, and ‘L’ LEDs on the 

Energi Savr Node

 QS unit(s) will flash sequentially in groups.

2. Use the 

Option

 button to select the scene wallstation type. A blinking LED indicates the selection: 

  •  ‘Def’ LED indicates a ‘scene + off’ wallstation (wallstation has a specific Off button)
  •  ‘Opt 1’ LED indicates a ‘scene’ wallstation (wallstation has no Off button)
3. To save the wallstation type, press and hold the 

Option

 button for 3 seconds. The LED for the selected 

wallstation type will flutter for 1 second, then remain steady.

4. To assign desired zone(s) to a wallstation, press and hold the 

Zone

 button for each desired zone for 

 

3 seconds. A blinking ‘Zone’ LED indicates an assigned zone. 

5. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds to save the 

settings.
To un-assign 

Energi Savr Node

 QS unit zones from a specific wallstation, press and hold the 

Zone

 button for 

the assigned zone(s) for 3 seconds. The ‘Zone’ LED will turn off to indicate success. 
Repeat for each desired wallstation-to-zone set-up that you wish to un-assign.

seeTouch QS Wallstation - Zone Toggle Type

1. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds. The QS link 

enters Programming Mode. The sensor Group A and Group B LEDs and the ‘H’, ‘M’, and ‘L’ LEDs on the 

Energi Savr Node

 QS unit(s) will flash sequentially in groups.

2. Use the 

Option

 button to change the wallstation type to zone toggle. A blinking LED will indicate the selection. 

 

Select ‘Opt 2’.

3. To save the wallstation type, press and hold the 

Option

 button for 3 seconds. The LED for the selected 

wallstation type will flutter for 1 second, then go to an on state.

4. To assign a specific wallstation button(s) to an 

Energi Savr Node

 QS unit zone, press the wallstation button you 

wish to assign (e.g. press button 1 – LED blinks slowly).

5. Press and hold the 

Zone

 button for the desired zone for 3 seconds. A blinking ‘Zone’ LED indicates an 

assigned zone.

6. Repeat steps 4-5 for each desired button-to-zone assignment.

7. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds to save the 

settings.
To un-assign 

Energi Savr Node

 QS unit zones from specific wallstation buttons, press and hold the 

Zone

 

button for the assigned zone(s) for 3 seconds. The ‘Zone’ LED will turn off to indicate success. 

GRAFIK Eye

 QS unit - Scenes and Off

1. Simultaneously press and hold the top and bottom scene buttons on the 

GRAFIK Eye 

QS unit for 3 seconds. 

The QS link enters Programming Mode. The sensor Group A and Group B LEDs and the ‘H’, ‘M’, and ‘L’ LEDs 

on the 

Energi Savr Node

 QS unit(s) will flash sequentially in groups.

2. To assign desired zone(s) to a 

GRAFIK Eye

 QS unit, press and hold the 

Zone

 button for the desired zone for 3 

seconds. A blinking ‘Zone’ LED indicates an assigned zone. 

3. Simultaneously press and hold the top and bottom scene buttons on the 

GRAFIK Eye 

QS unit for 3 seconds to 

save the settings.

Summary of Contents for Energi Savr Node QS QSNE-4S10-D

Page 1: ...nctionality 2 Programming 3 Input Programming Mode 3 Sensor Overview 3 Advanced Button Programming 4 Scene Programming Mode 4 QS Link Input s Setup 6 Contact Information 8 Energi Savr NodeTM QS Programming Guide Model QSNE 4S10 D ...

Page 2: ...compatible transmitters QS Wallstations All seeTouch QS wallstations are Scene keypads by default Scenes 1 16 will turn all the lights On Scene Off will turn all the lights Off Contact Closure Input CCI The CCI behaves as an Emergency Contact Closure Input If the CCI is open the Energi Savr Node QS unit will enter Emergency Mode which will turn on all loads and disable local zone control and contr...

Page 3: ... first unassociate any previously assigned sensors from that zone including those in out of box mode Only sensors powered directly from the Energi Savr Node QS unit will flash Sensor Overview Occupancy Sensors Energi Savr Node QS units are programmable to turn lights on and off based on room occupancy detected by compatible occupancy sensors To ensure proper operation of the Energi Savr Node QS un...

Page 4: ...nsor Use the and buttons to select response mode H LED indicates Occupancy mode Auto on off M LED indicates Vacancy mode Manual on auto off Opt1 Set daylight sensor setpoint for each zone Use the button to increase the set point Use the button to decrease the set point 4 Repeat steps 2 and 3 for each desired zone 5 Simultaneously press and hold the Program and Input buttons for 3 seconds to exit Z...

Page 5: ... indicated by flashing Option LEDs as shown ion the chart below LED Legend steady on flashing off LEDs Scene LEDs Scene LEDs Scene LEDs Scene Scene 5 Scene 6 Scene 7 Scene 8 Scene 9 Scene 10 Scene 11 Scene 12 Scene 13 Scene 14 Scene 15 Scene 16 3 Use the and buttons to set the selected scene to On or Off The H M and L LED group indicates your choice all LEDs on On all LEDs off Off 4 To make a zone...

Page 6: ...ld the top and bottom buttons on the wallstation for 3 seconds The QS link enters Programming Mode The sensor Group A and Group B LEDs and the H M and L LEDs on the Energi Savr Node QS unit s will flash sequentially in groups 2 Use the Option button to change the wallstation type to zone toggle A blinking LED will indicate the selection Select Opt 2 3 To save the wallstation type press and hold th...

Page 7: ...sociated to a QSE IO contact closure interface that is set in the Zone Toggle or Occupancy DIP configuration In the Zone Toggle configuration this can be used to toggle zones on your Energi Savr Node QS unit from third party equipment using contact closure inputs into the QSE IO or to monitor the state on or off of the zones on your Energi Savr Node QS unit from third party equipment using contact...

Page 8: ...a Centre Singapore 089316 TEL 65 6220 4666 FAX 65 6220 4333 Technical hotlines France 0800 90 12 18 Germany 00800 5887 6635 Italy 800 979 208 Spain 900 948 944 Northern China 10 800 712 1536 Southern China 10 800 120 1536 Hong Kong 800 901 849 Singapore 800 120 4491 Taiwan 00 801 137 737 Thailand 001 800 120 665853 Other Areas in Asia 65 6220 4666 Lutron Electronics Co Inc 7200 Suter Road Coopersb...

Reviews: