Timer Test Mode
1. Remove the retainer cover.
2. Rotate the black timer adjustment knob to
about midway (12 o’clock).
3. Return setting to minimum setting (full CCW).
Note:
The timer will remain in the 8 second test
mode for 1 hour, then automatically reset to
8 minutes.
4. To manually take the timer out of the 8 second test mode,
turn the timer adjustment approximately 1/16 in (1.6 mm)
clockwise to make the setting slightly above minimum (just
above the 8 minute setting).
Factory
Settings
12 o’clock
Full CCW
Factory Settings
ON
ON
ON
ON
A
1
2
3
4
B
1
2
3
4
Black: Timer
8 minute
default
Blue: Photo cell
(-R models only)
100% default
Red: Infrared
sensitivity
75% default
Green: Ultrasonic
range
50% default
Recommendation:
Leave sensitivity settings as shipped.
Note:
Not all models have every knob.
Control Settings (Blue Knob)
-R models only
0
1000
0
1000
0
1000
Minimum (low):
Lights will never come on, even though
room is occupied.
Maximum (high):
Photo cell has no effect on operation
(factory setting).
Normal:
200 lx to 600 lx is normal range.
Lighting
Control
system
Red (+20 to 24 V
-
)
Gray (control: occupancy & photo cell signal)
Black (common)
Yellow/White (NO)
Black/White (NC)
Blue/White (Relay Common)
Choose wire based on functionality:
• Yellow/White: NO (normally open)
Open: Unoccupied
Closed: Occupied
• Black/White: NC (normally closed)
Open: Occupied
Closed: Unoccupied
Cap off unused wire.
Wiring Diagrams
Relay Model Option:
-R models only
Blue: Cap off
Sensor Adjustments
Gray wire: logic with photo cell active:
Adjusting the “Lights Not On” Level
-R models only
1. Ensure ambient light is at desired level.
2. Place sensor in Test Mode as indicated above.
3. Set photo cell: Turn the blue knob full clockwise (lights
on no matter how bright the natural light is), then about
30˚ counterclockwise.
4. Check for Lights-Out: Move from underneath the
sensor, and remain still until the lights turn off. Move
around normally to turn the light on.
5. Adjust to desired level: If lights turn on, adjust the blue
knob another 30˚ counterclockwise and repeat step 3
until the lights remain off.
Note:
Set blue knob to 100% to disable photo cell
functionality and leave secondary dry contact closure
output functionality intact.
Room First Occupied
Light Level
Lights
Below set value
Turn on
Above set value
Remain off
During Occupancy
Light Level
Lights
Falls below set value
Turn on
Moves above set value
Remain on
Relay Output