Quick Start Guide
ALD-D48 Enclosure
Rough-In Installation
For more detailed installation, configuration, programming, and operating
instructions, refer to the
ALD-D48
Instruction Manual available on-line at
www.amx.com
.
Items in The Box
Optional Accessories
Installation
1.
Mount Rough-In Enclosure using following methods (mounting
hardware is not provided):
a. Surface Mount - Use keyholes shown in Figure 1 with bolts
sufficient for 50 lbs. (9kg) load (1/4" (M6) bolts recommended).
b. Recess Mount - Use screws through the right side of the panel
sufficient for 50 lbs. (9 kg) load. Mount panel flush to or not more
than 1/8" (3mm) below the finished wall surface. Panel is 2-7/8"
(6.2cm) deep past cover mounting tabs.
Caution:
•
Suitable for mounting in a vertical position only. Do not mount or place
the unit in a horizontal where the vent holes in the front are facing up.
•
This equipment is air-cooled. Mount in a location where the vented
cover will not be blocked.
•
Internal relays will click while in use. Mount in a location where such
noise is acceptable.
•
All wiring must be in accordance with national and local electrical
codes.
Danger:
Locate and lock supply breaker in the OFF position before wiring
to power terminal blocks.
2.
Run 120V power wiring into the panel. Locations to run power wiring
into the panel are shown in Figure 1. Terminal blocks will accept 26
through 14 AWG wire. Tighten terminal blocks to 3.5 to 5 in-lbs. (.40 to
.57 Nm). Do not overtighten.
3.
Install the ALD-D48 Processor in accordance with instructions
provided with the board.
4.
If not installing the board at this time, leave these instructions inside
the enclosure.
5.
Install cover. Ensure the vents are on the right side of the cover.
Tighten screws to 20 in-lbs. (2.3 Nm).
What You Will Find
Description
Item Number
Rough-In enclosure with cover
MA2604-01
includes 15VDC Power Supply
57-0425
ALD-D48 Controller Board Assembly
MA2604-02
includes controller hardware pack
Quick Start Guides
ALD-D48 Controller Assembly
93-2604
ALD-D48 Enclosure Rough-In
93-2604-01
Optional Accessories
Description
Item Number
ALD-1000D, 1000 W/VA Vareo Dimmer
FG2604-10
ALD-600D, 60 W/VA Vareo Dimmer
FG2604-20
ALD-1000NS, 1000 W/VA Vareo Switch
FG2604-30
ALD-VETS-R, Auxiliary Switch for Vareo
FG2604-40
ALD-VWP-2, 2 Gang Wallplate
FG2604-60
ALD-VWP-3, 3 Gang Wallplate
FG2604-61
ALD-VWP-4, 4 Gang Wallplate
FG2604-62
FIG. 1
ALD-D48 Rough-In enclosure
FIG. 2
Recommended cutout (not to scale)
Vented cover
120V power supply
Surface
mount
keyholes
Rough-In
enclosure
9.37
17.37
9.59
0.11
.55
.55
0.06
.06
13.00
2.06
Enclosure
cover
outline
.55"
(1.40 cm)
13.00" (33.02 cm)
9.37"
(23.80 cm)
.55"
(1.40 cm)
0.06"
(0.15 cm)
17.37" (44.12 cm)
.06"
(0.15 cm)
9.59"
(24.36 cm)
0.11"
(0.28 cm)
2.06" (5.23cm)
R0.125