3-14
CDD3000-HF Operation Manual
3 Installation
Figure 3.7 Mains connection
Attention: Danger to life! Never wire or disconnect electrical
connections while they are live! Before working on the device
disconnect the power. Wait until the DC-link voltage at
terminals X1/L+ and L- has fallen to
≤
60 V before working on
the device.
Note the following points:
•
Only all-current sensitive fault current breakers suitable for
CDD3000-HF drive controller operation may be used.
•
Switching the mains power: Cyclic power switching is permitted
every 120 seconds; jog mode is not permitted.
−
If switching is too frequent, the device protects itself by means
of high-resistance isolation from the system.
−
After a rest phase of a few minutes the device is ready to start
once again.
•
TN network and TT network: Permitted without restriction.
•
IT network: Not permitted!
−
In the event of a ground fault the voltage stress is around twice
as high, and creepages and clearances to EN50178 are no
longer maintained.
CDD34.xxx-HF
CDD32.xxx-HF
X1
L1
N
L1
K1
K1
L2
L3
L1
N
X1
L3
L1
L2
FN
< 0,3 m
3 x 400/460 V
1 x 230 V
Please note that the
mains power cable and
fuses used must
conform to the
specified listings (such
as cUL, CSA).