3.4 Global settings
The global settings page is divided in five sub menus:
CONTROL SOURCE
Here, you can set the type of protocol, the universe number, and the controller IP address for each control
source. If the IP address 0.0.0.0 is used all devices in the network generating the assigned control protocol
and universe can be the control source. The LumiNode will use an LTP merging policy between the first
four sources that become available. When using sACN the priority is also important to consider.
Each control source can be a different protocol, universe, and controller IP.
Press
Save
to apply your settings.
DEVICE SETTINGS
In this menu, you can set:
Short name. Enter a name of maximum 17 characters to indicate the node on Art-Net. The following
characters cannot be used: ^[ -~]*$.
Long name. Enter a name of maximum 63 characters to indicate the node on Art-Net. The following
characters cannot be used: ^[ -~]*$.
ID number of the LumiNode. The ID number is used for indication only.
Press
Save
to apply your settings.
DEVICE INFO
The device info window shows the MAC address and serial number of your device.
CONTACT CLOSURE
In this menu you can setup the details for the contact closure.
Protocol
can be Art-Net or sACN.
Universe
is the universe created by the contact closure.
Destination IP/Priority
allows you to broadcast or unicast the contact closure’s universe when using
Art-Net. If no IP is entered the broadcast address will be auto filled. When sACN is chosen as protocol this
becomes the priority.
Channel
is the control channel created by the contact closure.
Open
is the value (0-255) of the control channel when the contact is open.
Closed
is the value (0-255) of the control channel when the contact is closed.
Press
Save
to apply your settings.
The following values are linked to the options Switch, Play and Backup: (these can be found under the
question mark symbol on the Global Settings page/Contact Closure)
General
x
Do Nothing: 0 - 7
Switch
x
8 - 15: Input 1
x
16 - 23: Input 2
3 | ConfIGuratIon