EN
26
Low value
timer threshold
When the analog
output is lower that
this value, the corre
-
sponding counter is
incremented on each
second.
0.00 – 24.00 mA
(current)
0.00 – 12.00 V
(voltage)
0.00
High value
timer threshold
When the analog
output is higher that
this value, the corre
-
sponding counter is
incremented on each
second.
0.00 – 24.00 mA
(current)
0.00 – 12.00 V
(voltage)
0.00 –
24.00
mA
(current)
0.00 –
12.00 V
(voltage)
Alarm value
(power on and
timeout)
Output value in case of
power on and timeout.
The analog output will
take this value when
the module turns
on, or if the output
is not refreshed (by
an external Modbus
Master or an integrated
Master server) after a
time specified in the
“Timeout” field.
0.00 – 24.00 mA
(current)
0.00 – 12.00 V
(voltage)
0.00
Timeout
Timeout value. The
analog output will take
the alarm value if is not
updated after the set
time. This feature is
disable is a '0.0' value
is set.
0.0 – 3 000.0 s
0.0 s
Output current
range
Current output only.
Define the current
range of the output.
0...20 mA
4...20 mA
0...20
mA
(current
output
only)
Slave address
to check
Master mode only.
Set the address of the
Slave to read.
0...247
0