9. SIGNALLING OF ERRORS
Character messages signalling the incorrect controller operation.
Connect the controller supply again.
When this does not help, contact the
nearest authorized workshop service.
Error code
(upper displ.)
Overflow of the
measuring range
downwards or lack
of RTD
Check, if the type of selected sensor is
compatible witrh the connected one.
Check if input signal values is
contained in the suitable range
- If yes, check if the RTD is not
shorted or the thermocouple is not
inversely connected.
Overflow of the
measuring range
or break in the
sensor circuit
Check, if the type of selected sensor is
compatible witrh the connected one.
Check if input signal values is
contained in the suitable range
- If yes, check if there is no break in
the sensor circuit.
Input discalibrated
Reason
Procedure
ErrPV-Hi
ErrPV-Lo
Err.Cal
Table 2