P30P-09A 11 User's manual
5.2. Power-on messages
After connecting the external signals and turning the power on accompanied by turning the
green LED (power indicator) on, transducer displays the type, current software version and the serial
number. If the transducer is equipped with Ethernet interface (P30P-XX2XXXXXXX), then after
displaying the serial no., the device displays also the IP address saved in memory or received from
DHCP server.
Fig.5 Starting messages of the transducer not equipped with Ethernet interface
Fig. 6 Starting messages of the transducer equipped with Ethernet interface
The transducer automatically switches to the operating mode of measurement and processing
the analog output signal after approx. 3 seconds. Measured value is displayed in the upper line of the
display, the additional information is displayed in the lower line, see 5.5.4).
LED display shows the RS-485 transmission status, internal memory usage and alarm status. Ethernet
services (WWW server, FTP server, Modbus TCP/IP) are started for transducers equipped with Ethernet
interface.
5.3. Functions of the buttons
5.3.1. Functions of single buttons
- confirm button
●
entering the programming mode (hold the button for at least 3 seconds),
●
menu item selection – level selection,
●
entering the parameter value change mode,
●
accepting the altered parameter value,
●
change of content displayed on the bottom line of the display
●
turning the transducer on and holding down the button - entering into software update mode via