14
The configuration of the individual characteristic of analog outputs
amounts to the introduction of suitable values X1, X2, Y1, Y2 in cor-
responding registers to them from the range 4007 – 4014
tab.3
. Values
introduced in these registers must be integral values corresponding to
set point values multiplied by the value 100.
Example 1
Configuration of the individual characteristic of the first current analog
output (temperature):
The temperature conversion in the range -12.25
o
C
÷
77.75
o
C
into the
analogue current signal from the range 4.5
÷
18.5 mA is expected.
Table 3
Name Register
address Value
X1 temperature
4007 -1225
Y1 current
4008 450
X2 temperature
4009 7775
Y2 current
4010 1850
Fig.8. Individual Characteristic of Analog outputs