The  configuration  of  the  individual  characteristic  of  analog  outputs 

amounts  to  the  introduction  of  suitable  values  X1,  X2, Y1, Y2  in  cor-

responding registers to them from the range 4007 – 4014 

tab.3

. Values 

introduced in these registers must be integral values corresponding to 

set point values multiplied by the value 100.

4.3.  RS-485 Interface
4.3.1. Description of the MODBUS Protocol Implementation

The  implemented  protocol  is  in  compliance  with  the  PI-MBUS-300  

Rev  G  Modicon  Company  specification.  Following  functions  of  the  

MODBUS have been implemented in P18 transducers:

Example 1

Configuration of the individual characteristic of the first current analog 

output (temperature):

The  temperature  conversion  in  the  range  -12.25

o

C  ÷  77.75

o

C  into  the 

analogue current signal from the range 4.5...18.5 mA is expected.

Exemplary Configuration of the  

Individual First Analog Output Characteristik 

Table 3

  Name 

Register address 

Value

  X1 temperature  

4007 

-1225

  Y1 current  

4008 

450

  X2 temperature  

4009 

7775

  Y2 current  

4010 

1850

 

Code 

Meaning

 

03 (03h) 

Readout of n-registers

 

16 (10h) 

Write of n-registers

 

17 (11h) 

Identification of the slave device

Functions of the MODBUS Protocol Implemented  

in P18 Transducers 

Table 4

Summary of Contents for P18-0

Page 1: ...USER S MANUAL TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE...

Page 2: ......

Page 3: ...1 Assembly 5 3 2 Electrical Connections 7 4 SERVICING 9 4 1 Functions of the P18 Transducer 10 4 2 Individual Characteristic of Analog Outputs 11 4 3 RS 485 Interface 13 4 4 Standard Parameters 18 5...

Page 4: ......

Page 5: ...of the user s manual According to this basic safety information qualified skilled personnel are persons who are familiar with the installation assembly commis sioning and operation of the product and...

Page 6: ...Fig 1 Overall Dimensions of the P18 Transducer Fig 2 Lay out of Assembly Holes of the P18 Transducer...

Page 7: ...tions one must use a round wire with external dia meter from 3 5 mm up to 6 mm Before the transducer assembly one must pass supplying wires through the packing Twist the packing seal in order to obtai...

Page 8: ...er with current outputs Transducer with voltage outputs One must use a spiral for the interface line connection In case of the transducer work in an environment with high interference one must apply s...

Page 9: ...equipped of one two colour signalling diode The diode pulsation means pulsing in green colour measurements carrying out correctly pulsing in red colour correct communication through the RS 485 interf...

Page 10: ...humidity RH measured dew point a 2 1668 Pws RH 100 T 273 2 Td Tn m 1 log Pws RH 10000 A Coefficients for the dew point Table 2 T A m Tn 0 o C 6 119866 7 926104 250 4138 0 50 o C 6 1078 7 5 237 3 50 1...

Page 11: ...er the transducer determines from the system of equations coefficients a and b of the individual characteristic Value X1 In on the transducer input value Yi Out on the analog output Value X2 In on the...

Page 12: ...Following functions of the MODBUS have been implemented in P18 transducers Example 1 Configuration of the individual characteristic of the first current analog output temperature The temperature conve...

Page 13: ...value is located i two successive 16 bit registers Registers contain the same data as 32 bit registers from the area 7500 7512 Registers are only for readout 7500 7512 float 32 bits The value is loca...

Page 14: ...nge of transmission parameters 0 1 Acceptation of transmission para meter changes2 0 lack of operation 1 acceptation of changes 4005 Measurement averaging time 6 3600 Measurement averaging time given...

Page 15: ...sducer with voltage analog outputs Bit 2 1 the interval of averaging measurement result is expired Bit 3 4 0 0 steering up of 1 analog output temperature 0 1 steering up of 1 analog output relative hu...

Page 16: ...002 7501 Temperature T Temperature o C 7004 7502 Relative humidity RH Relative humidity 7006 7503 Dew point Td Dew point o C 7008 7504 Absolute humidity A Absolute humidity g m3 7010 7505 Min T Minimu...

Page 17: ...mA x 100 0 V x 100 X2 humidity 0 10000 o C x 100 10000 x 100 Y2 humidity 0 2000 mA x 100 1000 V x 100 4 4 Standard Parameters Standard Parameters of the P18 Transducer Table 8 In case when standard co...

Page 18: ...18 Fig 5 Placement of the Jumper Setting Temporary Communication Parameters...

Page 19: ...e filter Casing made of PCV Membrane of teflon lamina ted by a film Pore size 1 m Mean filtration effect Maximal temp up to 80 o C Response time t10 90 15 s Building automation In rooms with low pollu...

Page 20: ...c error of temperature conversion calculated quantities 0 5 of the range absolute humidity a g m3 dew point temperature Td o C additional errors temperature influence 25 of the basic error 10 C RS 485...

Page 21: ...lity noise immunity acc to EN 61000 6 2 noise emission acc to EN 61000 6 4 Security requirements acc to EN 61010 1 installation category III pollution grade 2 phase to earth working voltage 50 V altit...

Page 22: ...tection shield acc to the table 9 e g the shield coded 0874 490 014 means a filter made of sintered bronze The code will be established after agreement with the manufacturer Temperature and Humidity T...

Page 23: ...en used in compliance with the instructions the Manufacturer garantees to repair it free of charge 2 After the guarantee period One should turn over the transducer to repair it in a certified service...

Page 24: ...x 48 68 325 40 91 e mail export lumel com pl P18 07B SALES PROGRAM DIGITAL and BARGRAPH PANEL METERS MEASURING TRANSDUCERS ANALOG PANEL METERS DIN INSTRUMENTS DIGITAL CLAMP ON METERS INDUSTRIAL PROCES...

Reviews: