h. Determine which holes in the exit frame will be used for mounting 

(see fig.1 & fig.3). Support frame by two blocks of wood, maxi-
mum one inch apart. Strike knockouts with a hammer and screw-
driver. Clear holes of burrs to allow proper assembly of nipple/
wire assembly.

i. Secure canopy to the frame using the provided nipple/wire 

assembly.  Make sure the gasket washers are between the can-
opy and frame, and the nuts inside the exit sign (see fig. 3).

j. Reassemble the electronic module inside the frame.

Wall Mount (Single Face Model Only)

a. Remove the backplate from the packaging.  Determine the proper 

knockouts to remove for mounting to a junction box (see fig.4).
For 

Nexus

 option, install the liquid tight fitting, provided with the 

unit (see fig. 4).

b. Support area around knockouts with two blocks of wood. Strike 

knockouts from the inside with a hammer and a screwdriver.

c. Mount parts 11, 12, 15, 17 & 19 to backplate, as shown in fig. 4, 

and reinstall the backplate to the frame using the 4 tamper-proof 
screws (use the supplied bit).

2.

Electrical connections:

 Using the sealed AC nipple/wire assembly 

(3 wires), connect one end to the transformer leads, inside the enclo-
sure, and the other end, to AC line voltage inside the junction box.  
Connect the white lead to neutral and the purple lead to AC line volt-
age (the input is universal 110 to 347 VAC). (See fig. 5).

Optional:

 For AC models used with DC remote power, the sealed 

DC nipple/wire assembly (2 wires) will also need to be installed.  One 
end connects to the LED-STRIP leads, inside the enclosure, and the 
other end to DC input inside the junction box.  Connect the red lead 
to positive, and the blue lead to the negative of the remote DC input 
(See fig. 5).

3.

For canopy mount:

 Attach the canopy backplate to the junction box 

using the junction box screws. Mount the frame and canopy assem-
bly to canopy back plate by using the provided securement screw.

For wall mount:

 Attach the frame to the junction box, using the junc-

tion box supplied screws.

4. Reinstall the diffuser and the EXIT panel (if required, remove the 

appropriate chevron).

5. Install the lens by using the 4 short and 2 long tamper-proof screws.

The tamper-proof screws should be equally torqued to approxi-
mately 5 lbs-in (0.6 N-m).

6. Energize AC.  Sign will illuminate.

Manual Testing (Self-Powered Models)

Operate the magnetic “test switch” by holding the provided magnet 
underneath the unit where indicated on the frame.  The AC pilot lamp will 
go out, the legend will flicker, but remain lit.  Remove the magnet.  The 
AC pilot light will turn on, the legend will flicker but remain lit.

Automatic Testing (Self-Powered Models)

The unit will perform an automatic self-test of 30 seconds every 30 days,
60 second every 60 days and a 90 minute self-test once a year.

Figure 3

Figure 4

Knockouts

Figure 5

Summary of Contents for LER3000 Series

Page 1: ...of wire length c Remove proper knockouts in canopy backplate for desired mounting position For Nexus option install the liquid tight fitting provided with the unit For Ceiling mount use the k out located on side of the unit opposite side of the diagnostic display For Side mount use the k out located on top of the unit see fig 4 d Feed unswitched AC wires through large hole in canopy mount ing plat...

Page 2: ... Connect the white lead to neutral and the purple lead to AC line volt age the input is universal 110 to 347 VAC See fig 5 Optional For AC models used with DC remote power the sealed DC nipple wire assembly 2 wires will also need to be installed One end connects to the LED STRIP leads inside the enclosure and the other end to DC input inside the junction box Connect the red lead to positive and th...

Page 3: ...mal operation No fault Service Required is OFF and one of the two internal LED blinks showing that the micro controller is active Faulty operation Service Required blinks Battery Alarm ON Charger Alarm OFF Check battery or replace battery Battery Alarm ON Charger Alarm ON Check LED strip Battery Alarm OFF Charger Alarm ON Check charger circuit Nexus models Nexus models use two local indicators One...

Page 4: ...lready be installed 4 Install the diffuser panel by snapping the top edges under the two top retention screws and then snapping the bottom edges under the two bottom retention screws see fig 11 5 The EXIT panel installs in the same manner if required remove the appropriate chevron 6 Install the lens by using the 4 short and 2 long tamper proof screws see fig 12 The tamper proof screws should be eq...

Reviews: