background image

MAINTENANCE

SPECIAL 
INSTRUCTIONS

WARRANTY

Depending on the degree of soiling of the medium, 
carry out a dry clean from time to time. In addition 
operate the dampers at least four times a year accord-
ing to the plant-specific conditions. This prevents the 
slat seals from sticking in closed state. The slide bear-
ings can be blown off using compressed air as required, 
although they are basically maintenance-free (lubrica-
tion). Otherwise the RGK models operate mainte-
nance-free.

Only LUCOMA genuine spare parts may be used for all 
repair and maintenance work. 

ATEX: 

All relevant national and international stand-

ards and regulations for Ex zones must be observed.

Before using LUCOMA dampers in areas with increased 
requirements, report the prevailing conditions to the 
manufacturer so that the correct damper materials can 
be selected. 

The correct damper materials are especially important 
in factories with chemically laden atmospheres, elec-
troplating shops, battery rooms etc.

When installed and operated properly, the warranty 
according to the Swiss Code of Obligations is 2 years.

ATEX:

 Dampers operated in ATEX zones should be 

replaced every 10 years for safety reasons.

LUCOMA AG  

 

     

Weekendweg 5  ·  CH-3646 Einigen Switzerland 

               

Page 3/June 2017

       T41 33 655 00 44  ·  Fax +41 33 655 00 45  ·  www.lucoma.com  ·  [email protected]

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS