MAINTENANCE
SPECIAL
INSTRUCTIONS
WARRANTY
Depending on the degree of soiling of the medium,
carry out a dry clean from time to time. In addition
operate the dampers at least four times a year accord-
ing to the plant-specific conditions. This prevents the
slat seals from sticking in closed state. The slide bear-
ings can be blown off using compressed air as required,
although they are basically maintenance-free (lubrica-
tion). Otherwise the RGK models operate mainte-
nance-free.
Only LUCOMA genuine spare parts may be used for all
repair and maintenance work.
ATEX:
All relevant national and international stand-
ards and regulations for Ex zones must be observed.
Before using LUCOMA dampers in areas with increased
requirements, report the prevailing conditions to the
manufacturer so that the correct damper materials can
be selected.
The correct damper materials are especially important
in factories with chemically laden atmospheres, elec-
troplating shops, battery rooms etc.
When installed and operated properly, the warranty
according to the Swiss Code of Obligations is 2 years.
ATEX:
Dampers operated in ATEX zones should be
replaced every 10 years for safety reasons.
LUCOMA AG
Weekendweg 5 · CH-3646 Einigen Switzerland
Page 3/June 2017
T41 33 655 00 44 · Fax +41 33 655 00 45 · www.lucoma.com · [email protected]
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
RGK REGLAIR PRECISION CONTROL DAMPERS