Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
5 - 8 Installation
Issue 10 July 2000
Table 5-C provides widths for use with 350KCMIL cable.
Do not route other cable rack(s) above or through the area above the
rectifiers or any other heat source.
Run the output conductors in pairs (positive and negative). Distribute
the conductors evenly across the rectifier output racks. Pair the charge
cables in the cable rack.
Figure 5-5 shows how to run the dc output cables from two 400 ampere
rectifiers in a cable rack.
Table 5-C: Rack Widths for 350KCMIL Cables
Rack Width
Number of 400 Ampere Rectifiers
12
4
15
5
20
7
25
9
Figure 5-5: DC Output Cables in Cable Rack
Rect 2
–
–
–
–
+
+
+
+
Rect 1
Cable Rack