Lucent Technologies 60V Small Broadband Power System J85500Q-1
2 - 6 Product Description
Issue 4 October 1998
Certification
Considerations
CPS plants must be installed over non-combustible surfaces in
restricted access areas in accordance with Articles 110-16,
110-17, and 110-18 of the National Electric Code, ANSI/NFP
Number 70 or per requirements of applicable local codes.
Specifications
Table 2-A: ES664 Rectifier Specifications
Nominal Output Voltage
81.72 volts dc
Operating Output Voltage Ranges
72 - 85 volts dc
Operating Frequency Range
47-63Hz
Output Current
0 - 9.2 amperes
Nominal Input Voltage
100/120/200/208/240 volts ac
Input Voltage Ranges
90 - 130 volts ac
180 - 264 volts ac
Input Current
3.6 amperes @ 240 volts ac
7.28 @ 120 volts ac
Efficiency
86% typical @ 208/240 volts ac
Regulation
+0.5%
Ripple
50 millivolts peak to peak maximum over
the range 10 Hz to 20 MHz
Output Noise
32 dBrnc
Load Share Accuracy
1.25 amperes maximum
Heat Dissipation
111 watts (380 BTU/hr) maximum (Note
1)
Power Factor
>0.98 for loads > 60% full load
Total Harmonic Distortion
<5% for loads > 60% full load
Selective High-Voltage Shutdown
83.2 volts dc
Backup High-Voltage Shutdown
90 volts dc