Table 2-A: Lineage
®
2000 Battery Plant Specifications
(Model J85500D-3)
Input Voltage
180-264 volts ac (208/240 volts ac nominal)
Input Frequency
47-63 Hertz (50/60 Hertz nominal)
Operating Voltage
40-60.0 volts dc (48 volts dc nominal)
Float Voltage
47-58.5 volts dc (48 volts dc nominal)
Plant Current Rating
300 amperes
Plant Shunt
300 amperes maximum at 50 millivolts
LVD/R Voltage Settings
40.5 or 42.5 volts dc ±0.5V
LVLD/R Voltage
Disconnect voltage: 42V ±0.5V
Reconnect voltage: 50V ±0.5V
Controller
Basic: 113A type
Microprocessor option circuit pack: CP2
Datalogger option circuit pack: CP3
Rectifier Shelf Assembly
2 maximum, each mounts 3 rectifiers
Rectifiers
Type: Lineage
®
2000 SR50/-48V
Rating: -48 volts nominal, 50 amperes
Number: 6 maximum @ 16.5 Amps ac input (each)
Batteries
Type: Lineage
®
2000 2VR375E, 2VR250E or 12IR125
Rating: 375 Ah, 250 Ah or 125 Ah per string
Number: 6 strings maximum
Circuit Breakers
Type: KS23616
Ratings: 3, 5, 10, 15, 20, 30, 40, 45, 50, 60, 70, 80, 90,
100 amperes
Interrupt capacity: 10,000 amperes
Temperature
32-122 degrees Fahrenheit (0-50 degrees Celsius)
Altitude
-200 to 13000 feet (-61 to 3962 meters)
For altitudes of 5000 to 13,000 feet, derate maximum
temperature by 3.6 degrees Fahrenheit per 1000 feet
above 5000 feet. For altitudes of 1524 to 3962 meters,
derate maximum temperature by 0.656 degrees Celsius
per 304 meters above 1524 meters.
Framework
Type: 42 inch (1067 mm) high frame (standard 23 inch
relay rack width), mounted on top of a J85504C-1 or
J85504D-1 battery stand
Vertical mounting centers: 1.00 inches (25 mm)
Horizontal mounting centers: 22.32 inches (567 mm)