Lucent Technologies ECS Minicell Battery Plant H569-420
Issue 5 February 1997
Safety 4 - 1
4
Safety
Safety
Statements
Please read and follow all safety warnings before installing,
maintaining, or repairing the +24V Lineage
®
2000 battery plant.
1. The H569-420,+24V Minicell Lineage
®
2000 ECS Battery
Plant, is to be used in controlled environments. Install only
in restricted access areas (dedicated equipment rooms,
equipment closets, or the like) in accordance with articles
110-16, 110-17, and 110-18 of the U.S. National Electric
Code (NEC), ANSI/NFPA No. 70, and pursuant to
applicable local codes.
2. UL listed compression connectors should be used to
terminate UL listed field-wire conductors where required.
The listed connector should be applied only to the
appropriately sized conductors as specified by the
connector manufacturer using only the connector
manufacturer's recommended tooling or tooling approved
for that connector.
3. The H569-420, +24V Minicell Lineage
®
2000 ECS
Battery Plant, was evaluated for use in ambient
temperatures up to 50° Celsius.
4. Make all electrical connections using the proper crimping
tools and dies. Torque to values specified on H569-420.
5. Insulation on field-wired conductors should be rated no
less than 90° Celsius. Wire conductor size should be no
less than allowed by electrical codes for 60° Celsius wire
(regardless of insulation temperature rating used) and
based on the ampacity of the associated protection device.