A

Building Safety. Building Security.

•   Actuation and monitoring of up to 

127 extinguishing systems or 127 

fl ooding zones

•   Fully integrated into Fire Detection 

Control Panel Series BC216

•   Individual control panel or fl exibly 

expandable control panel network

•  Suitable for all system sizes
•  Optional hardware redundancy
•  EN 54, EN 12094-1, VdS certifi ed

Fire is a permanent threat to life and property. There-

fore, immediate response to a fi re is imperative. The 

main objective of the Extinguishing Control Panels Se-

ries LC216 is to alarm and to react in time and, conse-

quently, save lives and protect property. For decades 

LST have focused their aims to undertaking unrivaled 

efforts in order to realize new innovations in the security 

area. Research, development and production are loca-

ted within LST premises, thus guaranteeing fl exible and 

reliable individual solutions.

Using a 32-bit multiprocessor system, the Extinguishing 

Control Panels Series LC216 ensure topmost effi ciency 

and speed – prerequisites for saving lives and minimi-

zing damage to property.

Description

The  Extinguishing  Control  Panel  Series  LC216  is  an 

extended  Fire  Detection  Control  Panel  Series  BC216 

with additional functions for the control of extinguishing 

systems. Nevertheless, all functions of the fi re detec-

tion control panel remain intact. Therefore, a combined 

use as fi re detection and extinguishing control panel is 

provided as standard.

The Extinguishing Control Panels Series LC216 compri-

se the following types of control panels:

•   The Extinguishing Control Panel LC216-1 for an extin-

guishing system with one fl ooding zone according to 

EN 12094-1 or with up to 8 fl ooding zones without 

compliance to EN 12094-1.

•   The networked Extinguishing Control Panel LCnet216 

for up to 127 extinguishing systems. The LCnet216 

consists  of  several  sectional  control  panels,  which 

are  interconnected  via  the  Global  Security  System 

Network  GSSnet  and  thereby  form  a  decentralised 

extinguishing control system. Each extinguishing sys-

tem can control up to 32 fl ooding zones, and each 

LCnet sectional control panel can administrate up to 

8 fl ooding zones. A maximum of 127 fl ooding zones 

can be controlled by an Extinguishing Control Panel 

LCnet216.

The  Extinguishing  Control  Panel  Series  LC216  fulfi ls 

all compulsory requirements as well as the options of 

EN 12094-1, EN 54-2 and EN 54-4 and is VdS certi-

fi ed.

The  networked  Extinguishing  Control  Panel  LCnet216 

can be easily implemented with a redundant design of 

the extinguishing control.