Building Safety. Building Security.
• Addressable conventional technology
• Maximum temperature 57°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Extremely fl at design
• Sealed electronics
Description
The Thermal ROR Detector HT-11001 reacts to tempe-
rature changes within defi ned periods of time, up to a
maximum temperature of 57°C. The intelligent evaluati-
on of these data allows the early detection of spreading
fi res. The detector complies with Class A1R and can be
used up to a room height of 7.5m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. By
means of the optional Address Module NG60-1, each
detector can be addressed individually, thus allowing to
display the detector address, as well as an assigned
element text, on a suitable fi re detection control panel.
A detector fault is indicated by a yellow fl ashing of the
multicoloured status LED.
The detector can be attached to various bases and it
can be protected against theft.
Specifi cations
Operating voltage
Supply through the detector line voltage
Current consumption
typ. 65µA (quiescent)
Alarm temperature
57°C (maximum-heat component)
Operating temperature
max. +50°C
Ambient temperature
- 40°C to +70°C (no condensation or icing)
Relative humidity
0 – 98% (no condensation)
Dimensions ø × H
100 × 36 (mm)
Colour
white
Weight
70g
Approval
VdS G204033
Order number
242030
Order name
Thermal ROR Detector/Conv./ORBIS/Apo HT-11001