A

Building Safety. Building Security.

•  Addressable conventional technology
•  Alarm temperature 90°C
•   Individual detector addressing by 

means of optional address module

•   Optional connection of remote 

indicator

•   Sealed electronics

Description

Specifi cations

The Thermal Max Detector GM-55000-137 recognises 

a maximum temperature of 90°C as sign of fi re. It com-

plies with Class CS and can be used up to a room height 

of 6m.

Addressable conventional technology is used for alarm 

transmission  to  the  fi re  detection  control  panel.  By 

means of the optional Address Module NG60-1, each 

detector can be addressed individually. With that, the 

activated detector can also be safely identifi ed directly 

on the control panel.

The detector can be attached to various bases and it 

can be protected against theft.

Operating voltage 

Supply through the detector line voltage

Current consumption 

typ. 45µA (quiescent)

Alarm temperature 

typ. 90°C

Operating temperature 

max. +80°C (continuous operation)

Ambient temperature 

-20°C to +90°C (no condensation or icing)

Relative humidity 

0 – 95% (no condensation)

Dimensions ø × H 

100 × 42 (mm)

Colour 

white

Weight 

80g

Approval 

VdS G200062

Order number 

242027

Order name 

Thermal Max Detector/Conv./65/Apo GM-55000-137