background image

 

LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH

 - Wiegelestrasse 36  A-1231 

Wien  Austria 

 

Picture 6 & 7 - Power supply unit example schemes 

Picture 10 - Convention-
al line wiring (zone line 
EOL resistor inside of 
the device) 

www.lst.at 

  

L20-SGCWE-3000 (v1.0) 

MAIN MONITORING 

BACKUP MONITORING 

Picture 8 - Power 
supply monitoring 
lines wiring  

DEVICE WIRING - POWER SUPPLY 

 
The conventional system expander module must be 
power supplied either: 
 
- directly by the control panel or 
 
- from an external power source or 
 
- from an external power source with a power backup 
unit. 
 
Use the scheme at the right for connecting the power 
supply to the device. 
 
This terminal wiring scheme is always applied. 
 
If you want to use an external power source with a 
power backup unit, two additional module’s terminal 
blocks come in use: “MAIN MONITORING” and 
“BACKUP MONITORING”. 
 
“MAIN MONITORING” is a terminal that supervises the main power supply of an external power supply unit. 
 
“BACKUP MONITORING” is a terminal that supervises the backup power supply of an external power supply unit. 
 
Let’s have two examples of power supply units: 
 
 
 
 
 
 
 
 
 
 
 
 
 
“MAIN MONITORING” and “BACKUP MONITORING” lines will be connected to the module as in the following scheme: 
 
 
 
 
 
 

POWER SUPPLY 

Picture 5 - Power 
supply connection 
scheme 

DEVICE WIRING - CONVENTIONAL ZONE LINE

 

 
In order to connect this device to the conventional zone line, two types of schemes can be used, depending on the positioning of the 
expander module on the line: 
 
- the expander module is positioned at the beginning or in the middle of the zone line (conventional devices follow the device on the 
line or are positioned before and after it); therefore the zone line EOL resistor must be fitted externally as is normally done, but not 
into the device’s terminal blocks: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
- the expander module is positioned at the end of the zone line (all conventional devices are positioned before it); therefore the zone 
line EOL resistor must be fitted to the device’s terminals and not externally as normally is done.  
 
 
 

Picture 9 - Conventional 
line wiring (zone line 
EOL resistor outside of 
the device) 

IMPORTANT: please note that with this wiring 
configuration, if a fault occurs on the wireless 
sub-system, all the reminder conventional line, 
subsequent the expander, is isolated from the 
system until the fault itself is handled and 
reset; this occurs unless each sensor on the 
conventional line is equipped with a Schottky 
diode and the control panel provides for their 
use. 
 
Please refer to your applicable codes of prac-
tice and to your conventional control panel 
documentation. 

Reviews: