Building Safety. Building Security.

•  Addressable conventional technology
•   Alarm temperature 78°C
•   Individual detector addressing by 

means of optional address module

•   Optional connection of remote 

indicator

•   Function testable with Remote Test 

Unit ECO1000RTU

Description

The  Thermal  Max  Detector  ECO1004T  recognises  a 

maximum temperature of 78°C as sign of fi re. It com-

plies  with  Class  BS  and  can  be  used  up  to  a  room 

height of 6m.

Addressable conventional technology is used for alarm 

transmission  to  the  fi re  detection  control  panel.  By 

means of the Address Module NG58-1, each detector 

can be addressed individually.

A  test  activation  of  the  detector  can  be  carried  out 

using the Remote Test Unit ECO1000RTU. The detec-

tor can be attached to various detector bases and it 

can be protected against theft.

Specifi cations

Operating voltage 

Supply through the detector line voltage

Current consumption 

typ. 75µA (quiescent)

Alarm temperature 

typ. 78°C

Operating temperature 

max. +60°C

Ambient temperature 

-30°C to +70°C (continuous operation)

Relative humidity 

5 – 95% (no condensation)

Dimensions ø × H 

102 × 40.5 (mm)

Colour 

white

Weight 

70g

Approval 

VdS G202042

Order number 

242047

Order name 

Thermal Max Detector/Conv./1000/SS ECO1004T