5.23 Changed Parameter Display
This feature displays all the parameters that are different from the factory defaults.
Use this feature to track changed parameters.
Grou
p
Code
Name
Setting
Setting
Range
Unit
dr
89
Changed parameter
display
0
View All
-
-
Changed Parameter Display Setting Details
Code and
Features
Description
dr-89
Changed Para
Configuration
Function
0
View All
Display all parameters
1
View Changed Display changed parameters only
5.24 Timer Settings
Set a multi-function input terminal to a timer and On/Off control the multi-function
output and relay according to the timer settings.
Group Code
Name
Setting
Setting
Range
Unit
In
65
–69
Px terminal setting
options
38
Timer In
0
–52
-
OU
31
Multi-function relay 1
item
28
Timer Out
-
-
33
Multi-function relay 2
item
55
Timer On delay
3.00
0.00
–100
sec
56
Timer Off delay
1.00
0.00
–100
sec
Timer Setting Details
Code and
Features
Description
In.65
–69 Px
Define
Choose one of the multi-function input terminals and change it to a
timer terminal by setting it to 38 (Timer In).
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...