Stop) or 2 (Q-Stop Resume).
5.6 Dwell Operation
The dwell operation is used to maintain torque during the application and release of
the brakes on lift-type loads. Inverter dwell operation is based on the Acc/Dec dwell
frequency and the dwell time set by the user. The following points also affect dwell
operation:
•
Acceleration Dwell Operation:
When an operation command runs, acceleration
continues until the acceleration dwell frequency and constant speed is reached
within the acceleration dwell operation time (Acc Dwell Time). After the Acc Dwell
Time has passed, acceleration is carried out based on the acceleration time and
the operation speed that was originally set.
•
Deceleration Dwell Operation
: When a stop command is run, deceleration
continues until the deceleration dwell frequency and constant speed is reached
within the deceleration dwell operation time (Dec Dwell Freq). After the set time
has passed, deceleration is carried out based on the deceleration time that was
originally set, then the operation stops.
When dr.09 (Control Mode) is set to 0 (V/F), the inverter can be used for operations
with dwell frequency before opening the mechanical brake of lift-type loads, such as
an elevator.
Group Code
Name
Setting
Setting Range
Unit
Ad
20
Dwell frequency on
acceleration
5.00
Start frequency
–
Maximum frequency
Hz
21
Operation time during
acceleration
0.0
0.0
–10.0
sec
22
Dwell frequency during
deceleration
5.00
Start frequency
–
Maximum frequency
Hz
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...