background image

 

Programmable Logic Controller    Installation Guide 

Smart I/O                         XEL-BSSRT/F/H

 

This installation guide provides simple function information or PLC control. Please read 
carefully this data sheet and manuals before using products. Especially read precautions then 
handle the products properly.

 

 

■ 

Meaning of warning and caution label 

 

WARNING 

WARNING indicates a potentially hazardous situation which,   
if not avoided, could result in death or serious injury 

 

CAUTION 

CAUTION indicates a potentially hazardous situation which, 
if not avoided, may result in minor or moderate injury.   
It may also be used to alert against unsafe practices 

 

 

WARNING

 

 

Do not contact the terminals while the power is applied. 

 

Be sure there are no foreign metallic matters. 

 

Do not manipulate the battery(charge, disassemble, hitting, short, soldering). 

CAUTION

 

 

Be sure to check the rated voltage and terminal arrangement before wiring 

 

When wiring, tighten the screw of terminal block with the specified torque range 

 

Do not install the flammable things on surroundings 

 

Do not use the PLC in the environment of direct vibration 

 

Except expert service staff, Do not disassemble or fix or modify the product 

 

Use the PLC in an environment that meets the general specifications contained in 
this installation guide. 

 

Be sure that external load does not exceed the rating of output module. 

 

When disposing of PLC and battery, treat it as industrial waste. 

 

I/O signal or communication line shall be wired at least 100mm away from a high-
voltage cable or power line. 

 

 

To install, observe the below conditions.   

No 

Item 

Specification 

Standard 

Ambient temp. 

0 ~ 55

 

Storage temp. 

-25 ~ 70

 

Ambient humidity 

5 ~ 95%RH,    non-condensing 

Storage humidity 

5 ~ 95%RH,    non-condensing 

Vibration 

Resistance 

Occasional vibration 

Frequency 

Acceleration  Amplitude 

Number 

IEC 61131-2 

5≤f<8.4

 

3.5mm 

10 times in 

each 

direction 

for 

  X, Y, Z   

8.4≤f≤150

 

9.8

(1g) 

Continuous vibration 

Frequency 

Acceleration  Amplitude 

5≤f<8.4

 

1.75mm 

8.4≤f≤150

 

4.9

(0.5g) 

 

■ 

For system configuration, the following version is necessary. 

1) 

XG5000 Software   

 

: V4.30 or above 

 

■ 

For more information, please refer to user manual. 

Item 

Specification 

Communication protocol 

RAPIEnet, EtherNet/IP, Modbus-TCP, BOOTP, DHCP 

Transmission speed 

100/1000Mbps 

Communication cable 

Electric: S-FTP over CAT5e 

Optical: Multi-mode/Single-mode fiber optic cable(MMF/SMF) 

Maximum expansion stages 

8 slot 

Output current 

3.0A

*1)

 

Internal current consumption 

BSSRT: 710

, BSSRF: 750

, BSSRH: 730

 

*1) 

Be careful that the sum of the current consumption does not exceed the output current.

 

 

 This is front part of the product. Refer to each name when operating the system. For more 

information, refer to user’s manual.   


 
 
 
 
 
 
 
 
 
 
 

 

 Parts name and function 

No. 

Name 

Description 

 

Status LED 

RAPIEnet/IP Adapter operation status LED,   
Network communication status LED 

 

Rotary Switch 

Node Address switch 

 

Power connector 

DC24V power input connector 

 

Media connector 

Media connector (electric, optical) 

 

USB connector 

USB connector to connect with XG5000 

 

USB protection cover  Protection cover for USB connector 

 

Expansion cover 

Protection cover for expansion connector 

 

■ 

LED details

 

LED 

Status 

Description 

RUN 

Off 

Power Off 

Green On 

Master module is RUN 

Red On 

Master module is STOP 

Green Blink 

Waiting for service 

RMS 

Green On 

Normal 

Green Blink 

Devices setting is not complete 

Red On 

Non-restorable error occurs 

Red Blink 

Invalid setting, Restorable error occurs, 
Parameter errors, Initialization errors, 
Different speeds or duplexes between ports 

RNS 

Green On 

At least one connection 

Green Blink 

Device is not connected 

Red On 

Duplicated IP address/station number is detected 

Red Blink 

Time-out occurs with one or more devices 
Frame error or heartbeat error occurs 

RELAY 

Off 

Relay Off 

Green On 

Relay On 

LINK/ACT1 
LINK/ACT2 

Off 

Link=No, Activity=NA 

Green On 

1G Link=Yes, Activity=No 

Green Blink 

1G Link=Yes, Activity=Yes 

Yellow On 

10/100M Link=Yes, Activity=No 

Yellow Blink 

10/100M Link=Yes, Activity=Yes 

 

■ H

ere describes the method to attach each module to the base or remove it. 

1) Attachment of product 

  When extension input/output   

module is installed, pull two levers   
of adapter module up.   

  Push the product and connect   

it agreement with hook for fixation of 
four edges and hook    for connection 

  After connection, get down the hook 

For fixation and fix it completely 

2) Detachment of product 

  Push up the hook for disconnection. 

 Detach the product with two hands. (Don’t force it.)

 

 

Wiring 

 Installation of cable 

1) 

100/10000BASE-TX’s max.extended length between nodes is 100m. 

2) 

This module provides Auto Cross Over function so the user can use both cross and 
straight cable. 

Pin No. 

Sign 

Cable wiring 

 

Straight cable 

Cross cable 

TD+ 

1 ----- 1 

1 ----- 3 

TD- 

2 ----- 2 

2 ----- 6 

RD+ 

3 ----- 3 

3 ----- 1 

TRD2+ 

4 ----- 4 

4 ----- 7 

TRD2- 

5 ----- 5 

5 ----- 8 

RD- 

6 ----- 6 

6 ----- 2 

TRD3+ 

7 ----- 7 

7 ----- 4 

TRD3- 

8 ----- 8 

8 ----- 5 

 

Warranty 

■ Warranty period

 

18 months after the production date. 

■ Scope of Warranty

 

18-month warranty is available except: 

1) 

The troubles caused by improper condition, environment or treatment except the 
instructions of LS ELECTRIC. 

2) 

The troubles caused by external devices 

3) 

The troubles caused by remodeling or repairing based on the user’s own discretion. 

4) 

The troubles caused by improper usage of the product   

5) 

The troubles caused by the reason which exceeded the expectation from science 
and technology level when LS ELECTRIC manufactured the product   

6) 

The troubles caused by natural disaster   

■ C

hange in specifications 

Product specifications are subject to change without notice due to continuous product 
development and improvement.   

 

LS ELECTRIC Co., Ltd   

www.lselectric.co.kr

   10310001663 V1.2 (2020.4) 

 

 E-mail: 

[email protected]

 

 

 Headquarter/Seoul Office 

Tel: 82-2-2034-4033,4888,4703 

 LS ELECTRIC Shanghai Office (China) 

Tel: 86-21-5237-9977 

 LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) 

Tel: 86-510-6851-6666 

 LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam) 

Tel: 84-93-631-4099 

 LS ELECTRIC Middle East FZE (Dubai, U.A.E.) 

Tel: 971-4-886-5360 

 LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands) 

Tel: 31-20-654-1424 

 LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan) 

Tel: 81-3-6268-8241 

 LS ELECTRIC America Inc. (Chicago, USA) 

Tel: 1-800-891-2941 

 

 Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnam-

do, 31226, Korea 

Safety Precautions 

Use of environment 

Applicable Version 

Performance Specifications 

Parts name and Dimension (mm) 

Mounting & Installation 

C/N: 10310001663 