Function list
5.3 Function group 2
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
H 0
A300
[Jump code]
0-95
Sets the code number to jump.
1
O
H 1
A301
[Fault history 1] -
Stores information on the types of faults,
the frequency, the current and the
Accel/Decel condition at the time of fault.
The latest fault is automatically stored in
the H 1- [Fault history 1].
nOn
-
H 2
A302
[Fault history 2] -
nOn
-
H 3
A303
[Fault history 3] -
nOn
-
H 4
A304
[Fault history 4] -
nOn
-
H 5
A305
[Fault history 5] -
nOn
-
H 6
A306
[Reset fault
history]
0-1
Clears the fault history saved in H 1-5.
0
O
H 7
A307
[Dwell
frequency]
0.1-
400
[Hz]
When run frequency is issued, motor
starts to accelerate after dwell frequency
is applied to the motor during H8- [Dwell
time].
[Dwell frequency] can be set within the
range of F21- [Max frequency] and F23-
[Start frequency].
5.00
X
H 8
A308
[Dwell time]
0-10
[sec]
Sets the time for dwell operation.
0.0
X
H10
A30A
[Skip
frequency
select]
0 - 1
Sets the frequency range to skip to
prevent undesirable resonance and
vibration on the structure of the machine.
0
X
H11
1)
A30B
[Skip
frequency low
limit 1]
0.1-
400
[Hz]
Run frequency cannot be set within the
range of H11 thru H16. The frequency
values of the low numbered parameters
cannot be set above those of the high
numbered ones. Settable within the
range of F21 and F23.
10.00
X
H12
A30C
[Skip
frequency high
limit 1]
15.00
X
H13
A30D
[Skip
frequency low
limit 2]
20.00
X
H14
A30E
[Skip
frequency high
limit 2]
25.00
X
H15
A30F
[Skip
frequency low
limit 3]
30.00
X
H16
A310
[Skip
frequency high
limit 3]
35.00
X
1)
Only displayed when H10 is set to 1. # H17, H18 are used when F2, F3 are set to 1 (S-curve).
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...