XDesignerPlus Ver2.0 Communication Manual
11 / 13
PLC setup
PLC IP : 192 . 168 . 0 . 51
Communication Interface
Protocol : UDP
Settings
PLC Read Port : 2005
PLC Write Port : 2005
TOP Port : 1024
PLC Address : 00
Timeout : 1000 [mSec]
Delay time of transmission : 0 [mSec]
TOP IP : 192 . 168 . 0 . 50
TOP Ethernet setting communication diagnosis
Details
Contents
PLC IP
It is an IP address that external device was given.
Protocol
Select the protocol method either UDP or TCP.
PLC Read Port
It is the port address that will be used for ethernet of external device.
PLC Write Port
It is the port address that will be used for ethernet of external device.
TOP port
Setting the TOP port number to connect with external device.
PLC address [0~65535]
Address of other device. Select between [0 - 65535].
Timeout [ x1 mSec ]
Set up TOP’s waiting time from external device at [0 - 5000] x 1mSec.
Delay Time before
transmitting [ x1 mSec]
Set up TOP’s waiting time between response receiving – next command request transmission
from external device at [ 0 – 5000 ] x 1 mSec.
TOP IP
Setup the IP address that TOP receives in the network.
Port Settings
* Ethernet Communication
Ethernet Port
+ Network setting
Communication Interface
- MAC : 00 - 15 - ID - 00 - 30 - 52 (each device has different address)
Settings
- IP Address : 192. 168 . 0 . 50
- Subnet mask : 255 255 . 255 . 0
- Gateway : 192 168 . 0 . 1
Details
Contents
MAC
Physical official address in the network.
IP Address
Setup the IP address that TOP receives in the network.
Subnet mask
An address that divides the network ID and host ID regarding of IP address.
Gateway
An address that connects a network to another network.
4.2 TOP main menu setup item
- When a buzzer is on during the power reset, touch 1 spot at the upper LCD to move to "TOP Management Main" display.
- Set up driver interface at TOP according to below
Step1 → Step2
.
(Press “TOP ethernet setup” in
Step 1
to change setup at
Step 2
.)
Step 1
. [ PLC setup ] .Setup driver interface.
Step 1–Reference.
Step 2
. [PLC Setup] > [TOP Ethernet Setup] - Setup the serial parameter of correspond port.
Step 1–Reference.